p.5862025 Nonresidential Appendices (g) Verify that compressor panel control readings for “RPMs,” “% speed,” “kW”, and
p.586“amps” match the readings from the PLC or other control systems.
p.586(h) Verify that compressor nameplate data is correctly entered into the PLC or other
p.586control system.
p.586NA7.10.4.2 Functional Testing
p.586Step 1: Override any heat reclaim, floating suction pressure, floating head pressure and
p.586defrost functionality before performing functional tests.
p.586Step 2: Measure and document the current compressor operating suction pressure and
p.586saturated suction temperature.
p.586Step 3: Document the suction pressure/saturated suction temperature setpoint. Program
p.586into the control system a target setpoint equal to the current operating condition measured in Step 2. Allow 5 minutes for system to normalize. This will be referred to as the “test suction pressure/saturated suction temperature setpoint.”
p.586Step 4: Using the control system, raise the test suction setpoint in 1 psi increments until
p.586the compressor controller modulates to decrease compressor speed. Verify and document the following:
p.586(a) Compressor speed decreases.
p.586(b) Compressor speed continues to decrease to minimum speed.
p.586(c) Any slide valve or other unloading means does not unload until after the
p.586compressor has reached its minimum speed (RPM).
p.586Step 5: Using the control system, lower the test suction setpoint in 1 psi increments until
p.586the compressor controller modulates to increase compressor speed. Verify and document the following:
p.586(d) Any slide valve or other unloading means first goes to 100 percent before
p.586compressor speed increases from minimum.
p.586(e) Compressor begins to increase speed.
p.586(f) Compressor speed continues to increase to 100 percent.
p.586Step 6: Using the control system, program the suction target setpoints back to original
p.586settings as documented in Step 3.
p.586Step 7: Restore any heat reclaim, floating suction pressure, floating head pressure and
p.586defrost functionality.
p.586Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes