NA7.10.4.1 Construction Inspection

p.5852025 Nonresidential Appendices (d) Record the current refrigeration system condensing temperature/condensing

p.585pressure readings from the control system.

p.585(e) Document current head pressure control setpoints, including the TD setpoint.

p.585(f) Calculate and record the actual observed TD, defined as the difference

p.585between the dry bulb temperature and the refrigeration system SCT.

p.585(g) Confirm agreement between the current control system TD setpoint and the

p.585observed TD. If values are different, address and correct control system methods.

p.585Step 6: Document current minimum condensing temperature setpoint. Using the control

p.585system change the minimum condensing temperature setpoint to a value greater than the current operating condensing temperature. Verify and document the following:

p.585(a) Condenser fan controls modulate to decrease capacity.

p.585(b) All condenser fans serving common condenser loop modulate in unison.

p.585(c) Condenser fan controls stabilize within a 5 minute period.

p.585Step 7: Using the control system, reset the system head pressure controls, fan motor

p.585controls and minimum condensing temperature control setpoint to original settings documented in Steps 3 and 6.

p.585Step 8: Restore any heat reclaim, floating suction pressure, floating head pressure and

p.585defrost functionality. Reset the minimum condensing temperature setpoint to the value documented in Step 6.

p.585NA7.10.4 Variable Speed Screw Compressors

p.585Conduct and document the following functional tests on all variable-speed screw compressors.

p.585NA7.10.4.1 Construction Inspection

p.585Prior to functional testing, document the following:

p.585(a) Verify all single open-drive screw compressors dedicated to a suction group have

p.585variable speed control.

p.585(b) Verify all compressor suction and discharge pressure sensors read accurately (or

p.585provide an appropriate offset) using a standard.

p.585(c) Verify all input or control temperature sensors used by controller read accurately

p.585(or provide an appropriate offset) using temperature standard.

p.585(d) Verify that all sensor readings used by the compressor controller convert or

p.585calculate to the correct conversion units at the controller (e.g., saturated pressure reading is correctly converted to appropriate saturated temperature, etc.).

p.585(e) Verify that all compressor speed controls are operational and connected to

p.585compressor motors.

p.585(f) Verify that all speed controls are in “auto” mode.

p.585Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes