p.5832025 Nonresidential Appendices (e) Verify the ambient dry bulb temperature using a NIST traceable instrument,
p.5842025 Nonresidential Appendices (b) Observe control operation for at least 30 minutes to confirm stable control
p.583including verification of at least two different ambient readings. Calibrate if needed. Replace if outside manufacturer’s recommended calibration range.
p.584operation, as shown by condenser fan speed varying as compressor capacity changes, and not ranging from maximum to minimum fan speed or constant “hunting”. If required, adjust control response setpoints to achieve stable operation. Since condenser control settings require fine-tuning over time, this is often accomplished using control system history or visual trends, showing one hourly and daily operation.
p.583(f) Verify all ambient dry bulb temperature sensors are not mounted in direct sunlight
p.583or is provided within a suitable solar shield.
p.583(g) Verify that all sensor readings used by the condenser controller convert or
p.583calculate to the correct conversion units and are displayed at the controller (e.g., observed pressure reading is correctly converted to appropriate saturated temperature, etc.).
p.584Step 3: Identify control Temperature Difference
p.584(a) Record the current outdoor ambient air dry bulb and refrigeration system
p.584condensing temperature/condensing pressure readings from the control system. Note whether discharge pressure or a dedicated condenser pressure sensor is used for condenser pressure control.
p.583(h) Verify that all fan motors are operational and rotating in the correct direction.
p.583(i) Verify that all condenser fan speed controls operate automatically in response to
p.583changes in both pressure (SCT) and ambient temperature.
p.584(b) Document current head pressure control setpoints, including the
p.584Temperature Difference (TD) setpoint.
p.583NA7.10.3.3.2Functional Testing
p.584(c) Calculate and record the actual observed TD, defined as the difference
p.584between the dry bulb temperature and the refrigeration system SCT.
p.584(d) Confirm agreement between the current control system TD setpoint and the
p.584observed TD. If values are different, address and correct controls system methods.
p.584Step 4: Test adjusted control Temperature Difference (Setpoint1).
p.583Step 1: Verify mechanical controls and other strategies will not affect tests.
p.584(a) Enter a smaller TD value into the control system sufficient enough to cause an
p.583(a) Verify condenser pressure low-limit holdback and/or bypass regulating valves, if
p.584observable response, such as 1 to 2 degrees smaller, but not small enough to cause the system to operate continuously at 100% fan speed. Record this value as TD Test Setpoint 1.
p.583any, are set below the minimum SCT setpoint. Condenser pressure controls valves will cause fans to operate at 100% speed if they are not set below the minimum SCT value. In warm weather, this may require setting out of range, and deferring valve settings until cold weather allows valves to be adjusted.
p.584(b) Observe change in control system operation which should include an increase
p.584in fan speed and a decrease in condensing temperature.
p.583(b) Turn off any heat reclaim controls and any intermittent defrost pressure offset
p.584(c) Allow time for the control system to achieve stable operation.
p.583strategies that would affect condenser setpoint control.
p.584(d) Document current head pressure control setpoints, including the TD setpoint.
p.583(c) Document adiabatic mode switching setpoints, if necessary for test temporarily
p.583change the adiabatic mode setpoint such that the condenser operates in dry mode. Verify that the adiabatic pads are completely dry before beginning tests.
p.584(e) Calculate and record the actual observed TD, defined as the difference
p.584between the wet bulb temperature and the refrigeration system SCT.
p.583Step 2: Operate in control range and verify
p.584(f) Confirm agreement between the current control system TD setpoint and the
p.584observed TD. If values are different, address and correct control system methods.
p.583(a) Verify the condenser control value is operating in the variable setpoint
p.583control range, i.e., above the minimum SCT setpoint and below the maximum SCT setpoint.
p.584Step 5: Test adjusted control Temperature Difference (Setpoint2) Enter a TD value into
p.584the control system that is different from TD Test Setpoint1, sufficient enough to cause an observable response. Record this value a TD Test Setpoint2.
p.583i. If necessary, increase or decrease the system load.
p.583ii. If necessary, during low load or low ambient conditions with system observed at the minimum SCT, temporarily adjust the minimum SCT to a lower value, if the refrigeration system design will allow, or increase the control TD to result in a higher control value.
p.584(a) Observe change in control system operation which should include an increase
p.584in fan speed and a decrease in condensing temperature.
p.584(b) Allow time for the control system to achieve stable operation.
p.584(c) Record the current outdoor ambient dry bulb temperature.
p.583Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.584
p.584Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes