p.5822025 Nonresidential Appendices (d) If the refrigeration system is already operating at minimum saturated condensing
p.582temperature/head pressure, reverse Steps 4 and 5.
p.582Step 5: Using the control system, lower the test setpoint in 1 degree (or 3 psi) increments
p.582until the condenser fan control modulates to increase fan motor speed. Verify and document the following:
p.582(a) Fan motor speed increases.
p.582(b) All condenser fan motors serving common condenser loop increase speed in
p.582unison in response to controller output.
p.582Step 6: Document current minimum condensing temperature setpoint. Using the control
p.582system change the minimum condensing temperature setpoint to a value greater than the current operating condensing temperature. Verify and document the following:
p.582(a) Condenser fan controls modulate to decrease capacity.
p.582(b) All condenser fans serving common condenser loop modulate in unison.
p.582(c) Condenser fan controls stabilize within a 5 minute period.
p.582Step 7: Using the control system, reset the system head pressure controls, fan motor
p.582controls and minimum condensing temperature control setpoint to original settings documented in Steps 2 and 6.
p.582Step 8: Restore any heat reclaim, floating suction pressure, floating head pressure and
p.582defrost functionality. Reset the minimum condensing temperature setpoint to the value documented in Step 6.
p.582NA7.10.3.3 Adiabatic Condensers and Condenser Fan Motor Variable Speed Control
p.582Conduct and document the following functional tests on all adiabatic condensers.
p.582NA7.10.3.3.1Construction Inspection
p.582Prior to functional testing, document the following:
p.582(a) Verify the control system minimum Saturated Condensing Temperature (SCT)
p.582setpoint is at or below 70°F.
p.582(b) Verify the control system maximum SCT setpoint (if used) is at or near the system
p.582design SCT.
p.582(c) Verify accuracy of refrigerant pressure-temperature conversions and consistent
p.582use of either temperature or pressure for the controlled variable setpoint in the control system.
p.582(d) Verify the discharge pressure sensor (or condenser pressure if used) reads
p.582accurately, using a National Institute of Standards and Technology (NIST) traceable reference pressure gauge or meter. At the minimum, the discharge pressure sensor accuracy shall be verified at two different pressures within the typical operating range. Calibrate if needed. Replace if outside manufacturer’s recommended calibration range.
p.582Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes