p.5812025 Nonresidential Appendices (e) Verify all condenser inlet and outlet pressure sensors read accurately (or provide
p.581an appropriate offset) using a pressure standard.
p.581(f) Verify all ambient dry bulb temperature sensors used by controller read accurately
p.581(or provide an appropriate offset) using temperature standard.
p.581(g) Verify all temperature sensors used by the controller are mounted in a location that
p.581is not exposed to direct sunlight.
p.581(h) Verify that all sensor readings used by the condenser controller convert or
p.581calculate to the correct conversion units at the controller (e.g., saturated pressure reading is correctly converted to appropriate saturated temperature, etc.).
p.581(i) Verify that all fan motors are operational and rotating in the correct direction.
p.581(j) Verify that all condenser fan speed controls are operational and connected to
p.581condenser fan motors to operate in unison the fans serving a common condenser loop.
p.581(k) Verify that all speed controls are in “auto” mode.
p.581NA7.10.3.2.2 Functional Testing
p.581Step 1: Override any heat reclaim, floating suction pressure, floating head pressure and
p.581defrost functionality before performing functional tests.
p.581Document current outdoor ambient air dry bulb temperature and refrigeration system condensing temperature/condensing pressure readings from the control system.
p.581Step 2: Calculate and document the temperature difference (TD), defined as the
p.581difference between the dry bulb temperature and the refrigeration system saturated condensing temperature (SCT).
p.581Document current head pressure control setpoint.
p.581Step 3: Using the desired condenser fan motor cycling or head pressure control strategy,
p.581program into the control system a setpoint equal to the reading or calculation obtained in Step 2.
p.581This will be referred to as the “test setpoint.” Allow 5 minutes for condenser fan speed to normalize.
p.581Step 4: Using the control system, raise the test setpoint in 1 degree (or 3 psi) increments
p.581until the condenser fan control modulates to minimum fan motor speed. Verify and document the following:
p.581(a) Fan motor speed decreases.
p.581(b) All condenser fan motors serving common condenser loop decrease speed in
p.581unison in response to controller output.
p.581(c) Minimum fan motor control speed (rpm or percent of full speed).
p.581Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes