p.5802025 Nonresidential Appendices (e) All condenser fan motors serving common condenser loop decrease speed in
p.580unison in response to controller output.
p.580(f) Minimum fan motor control speed (rpm or percent of full speed).
p.580(g) If the refrigeration system is already operating at minimum saturated condensing
p.580temperature/head pressure, reverse Steps 4 and 5.
p.580Step 5: Using the control system, lower the test setpoint in 1 degree (or 3 psi) increments
p.580until the condenser fan control modulates to increase fan motor speed. Verify and document the following:
p.580(h) Fan motor speed increases.
p.580(i) All condenser fan motors serving common condenser loop increase speed in
p.580unison in response to controller output.
p.580Step 6: Document the current minimum condensing temperature setpoint. Using the
p.580control system, change the minimum condensing temperature setpoint to a value greater than the current operating condensing temperature. Verify and document the following:
p.580(j) Condenser fan controls modulate to decrease capacity.
p.580(k) All condenser fans serving common condenser loop modulate in unison.
p.580(l) Condenser fan controls stabilize within a 5 minute period.
p.580Step 7: Using the control system, reset the system head pressure controls, fan motor
p.580controls and minimum condensing temperature control setpoint to original settings documented in Steps 3 and 6.
p.580Step 8: Restore any heat reclaim, floating suction pressure, floating head pressure and
p.580defrost functionality. Reset the minimum condensing temperature setpoint to the value documented in Step 6.
p.580NA7.10.3.2 Air-Cooled Condensers and Condenser Fan Motor Variable Speed Control
p.580Conduct and document the following functional tests on all air-cooled condensers.
p.580NA7.10.3.2.1Construction Inspection
p.580Prior to functional testing, document the following:
p.580(a) Verify that the minimum condensing temperature control setpoint is at or below
p.58070°F.
p.580(b) Verify that the master system controller saturated condensing temperature input is
p.580the temperature equivalent reading of the condenser pressure sensor.
p.580(c) Verify all drain leg pressure regulator valves are set below the minimum
p.580condensing temperature/pressure setpoint.
p.580(d) Verify all receiver pressurization valves, such as the outlet pressure regulator
p.580(OPR), are set lower than the drain leg pressure regulator valve setting.
p.580Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes