NA7.10.3.1.2 Functional Testing

p.5792025 Nonresidential Appendices (e) Verify all condenser inlet and outlet pressure sensors read accurately (or provide

p.579an appropriate offset) using a pressure standard.

p.579(f) Verify all ambient dry bulb temperature sensors used by controller read accurately

p.579(or provide an appropriate offset) using a temperature standard.

p.579(g) Verify all relative humidity sensor used by controller read accurately (or provide an

p.579appropriate offset) using RH standard.

p.579(h) Verify all temperature sensors used by the controller are mounted in a location that

p.579is not exposed to direct sunlight.

p.579(i) Verify that all sensor readings used by the condenser controller convert or

p.579calculate to the correct conversion units at the controller (e.g., saturated pressure reading is correctly converted to appropriate saturated temperature; dry bulb and relative humidity sensor readings are correctly converted to wet bulb temperature, etc.).

p.579(j) Verify that all fan motors are operational and rotating in the correct direction.

p.579(k) Verify that all condenser fan speed controls are operational and connected to

p.579condenser fan motors to operate in unison the fans serving a common condenser loop.

p.579(l) Verify that all speed controls are in “auto” mode.

p.579NA7.10.3.1.2Functional Testing

p.579Step 1: Override any heat reclaim, floating suction pressure, floating head pressure and

p.579defrost functionality before performing functional tests.

p.579Step 2:

p.579(a) Document current outdoor ambient air dry bulb and wet bulb temperatures, relative

p.579humidity and refrigeration system condensing temperature/condensing pressure readings from the control system.

p.579(b) Calculate and document the temperature difference (TD), defined as the difference

p.579between the wet bulb temperature and the refrigeration system saturated condensing temperature (SCT).

p.579(c) Document current head pressure control setpoint.

p.579Step 3: Using the desired condenser fan motor cycling or head pressure control strategy,

p.579program into the control system a setpoint equal to the reading or calculation obtained in Step 2. This will be referred to as the “test setpoint.” Allow 5 minutes for condenser fan speed to normalize.

p.579Step 4: Using the control system, raise the test setpoint in 1 degree (or 3 psi) increments

p.579until the condenser fan control modulates to minimum fan motor speed. Verify and document the following:

p.579(d) Fan motor speed decreases.

p.579Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes