p.5782025 Nonresidential Appendices (c) All refrigerated space temperature and humidity sensors are verified to be
p.578mounted in a location away from direct evaporator discharge air draft.
p.578(d) Verify that all fan motors are operational and rotating in the correct direction.
p.578(e) Verify that fan speed control is operational and connected to evaporator fan
p.578motors.
p.578(f) Verify that all speed controls are in “auto” mode.
p.578NA7.10.2.2 Functional Testing
p.578Conduct and document the following functional tests on all evaporators.
p.578Step 1: Measure current space temperature or humidity. Program this temperature or
p.578humidity as the test temperature or humidity setpoint into the control system for the functional test steps. Allow 5 minutes for system to normalize.
p.578Step 2: Using the control system, lower test temperature or humidity setpoint in 1 degree
p.578or 1% RH increments below any control dead band range until:
p.578(a) Evaporator fan controls modulate to increase fan motor speed.
p.578(b) Evaporator fan motor speed increases in response to controls.
p.578(c) Verify and document the above.
p.578Step 3: Using the control system, raise the test temperature or humidity setpoint in 1
p.578degree or 1% RH increments above any control dead band range until fans go to minimum speed. Verify and document the following:
p.578(d) Evaporator fan controls modulate to decrease fan motor speed.
p.578(e) Evaporator fan motor speed decreases in response to controls.
p.578(f) Minimum fan motor control speed (rpm or percent of full speed).
p.578Step 4: Restore control system to correct control setpoints.
p.578NA7.10.3 Condensers and Condenser Fan Motor Variable Speed Control
p.578NA7.10.3.1 Evaporative Condensers and Condenser Fan Motor Variable Speed Control
p.578NA7.10.3.1.1Construction Inspection
p.578Prior to functional testing, document the following:
p.578(a) Verify the minimum condensing temperature control setpoint is at or below 70°F.
p.578(b) Verify the master system controller saturated condensing temperature input is the
p.578temperature equivalent reading of the condenser pressure sensor.
p.578(c) Verify all drain leg pressure regulator valves are set below the minimum
p.578condensing temperature/pressure setpoint.
p.578(d) Verify all receiver pressurization valves, such as the outlet pressure regulator
p.578(OPR), are set lower than the drain leg pressure regulator valve setting.
p.578Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes