p.436RA3.8 Field Verification and Diagnostic Testing of Air Leakage of Building
p.436Enclosures and Dwelling Unit Enclosures
p.436RA3.8.1 Purpose and Scope
p.436The purpose of this test procedure is to measure the air leakage rate through a building enclosure or a dwelling unit enclosure.
p.436The measurement procedure shall be based on the specifications of Residential Energy Services Network's (RESNET) Standard for Testing Airtightness of Building, Dwelling Unit, and Sleeping Unit Enclosures; Airtightness of Heating and Cooling Air Distribution Systems; and Airflow of Mechanical Ventilation Systems (ANSI/RESNET/ICC 380-2019) (RESNET 380) as further specified in Subsections RA3.8.2, RA3.8.3, RA3.8.4 below.
p.436This enclosure leakage procedure is applicable to:
p.436– Residential Field Verification and Diagnostic Test Protocolsp.437
p.4372025 Residential Appendices • Single family building enclosures
p.437• Multifamily dwelling unit enclosures