p.246JA9.2.3 Nominal Air-Handling Unit Airflow
p.246The nominal air-handling unit airflow used for determining the leakage criterion for qualification shall be as follows:
p.246(a) For heating-only systems the nominal air-handling unit airflow shall be 21.7 cfm
p.246per kBtu/hr of rated heating output capacity.
p.246(b) For systems that provide space cooling, the nominal air-handling unit airflow shall
p.246be 400 cfm per nominal ton of cooling capacity as specified by the manufacturer, or the heating-only value, whichever is greater.
p.246JA9.2.4 Leakage Criterion for Qualification
p.246Allowable leakage for qualification as a Low Leakage Air-Handling Unit shall be equal to or less than 1.4 percent of the nominal air-handling unit airflow determined by Section JA9.2.3.
p.246Appendix JA9 – Qualification Requirements for Low Leakage Air-Handling Units