p.475Section 160.2 – Mandatory Requirements for Ventilation and Indoor Air Quality
p.475(a) General requirements.
p.4751. Attached dwelling units in multifamily buildings shall comply with the applicable requirements of Subsection 160.2(b) below. Occupiable spaces in multifamily buildings other than attached dwelling units shall comply with the applicable requirements of Section 160.2(c). When field verification and diagnostic testing of attached dwelling units is required by Section 160.2, buildings with three habitable stories or fewer shall use the applicable procedures in the Residential Appendices, and buildings with four or more habitable stories shall use the applicable procedures in Nonresidential Appendices NA1 and NA2.
p.4752. The required outdoor air-ventilation rate and the air-distribution system design shall be clearly identified on the building design plans submitted to the enforcement agency in accordance with Section 10-103 of Title 24, Part 1.
p.475(b) Attached dwelling units. Attached dwelling units shall comply with the requirements of
p.475Subsections 1 and 2 below.
p.475A. System types specified in Subsections i, ii and iii shall be provided with air filters in
p.475accordance with Sections 160.2(b)1B, 160.2(b)1C and 160.2(b)1D. System types specified in Subsection i shall also comply with Section 160.2(b)1E.
p.475i. Mechanical space-conditioning systems that supply air to an occupiable space through
p.475ductwork exceeding 10 ft (3 m) in length.
p.475ii. Mechanical supply-only ventilation systems and makeup air systems that provide
p.475outside air to an occupiable space.
p.475iii. The supply side of mechanical balanced ventilation systems, including heat recovery
p.475ventilation systems, and energy recovery ventilation systems that provide outside air to an occupiable space.
p.475B. System design and installation.
p.475i. The system shall be designed to ensure that all recirculated air and all outdoor air
p.475supplied to the occupiable space are filtered before passing through any system's thermal conditioning components.
p.475ii. All systems shall be designed to accommodate the clean-filter pressure drop imposed
p.475by the system air filter(s). The design airflow rate, and maximum allowable clean-filterp.476
p.475SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
p.476pressure drop at the design airflow rate applicable to each air filter, shall be determined and reported on labels according to Subsection iv below.
p.476Systems specified in Section 160.2(b)1Ai shall be equipped with air filters that meet either Subsection a or b below:
p.476a. Nominal two-inch minimum depth filter(s) shall be sized by the system designer, or
p.476b. Nominal one-inch minimum depth filter(s) shall be allowed if the filter(s) are sized
p.476according to Equation 160.2-A, based on a maximum face velocity of 150 ft per minute and according to the maximum allowable clean-filter pressure drop specified in Section 160.2(b)1Dii.
p.476Aface = Qfilter /Vface (Equation 160.2-A)
Equation text: Aface = air filter face area, the product of air filter nominal length × nominal width, ft2.
Needs visual review
Equation text: Qfilter = design airflow rate for the air filter, ft3/min
Needs visual review
Equation text: Vface = air filter face velocity ≤ 150 ft/min
Needs visual review
p.476iii. All system air filters shall be located and installed in such a manner as to be accessible
p.476for regular service by the system owner.
p.476iv. All system air filter installation locations shall be labeled to disclose the applicable
p.476design airflow rate and the maximum allowable clean-filter pressure drop. The labels shall be permanently affixed to the air filter installation location, readily legible, and visible to a person replacing the air filter. v. Filter racks or grilles shall use gaskets, sealing or other means to close gaps around
p.476inserted filters and prevent air from bypassing the filter.
p.476C. Air filter efficiency. The system shall be provided with air filters having a designated
p.476efficiency equal to or greater than MERV 13 when tested in accordance with ASHRAE Standard 52.2, or a particle size efficiency rating equal to or greater than 50 percent in the 0.30–1.0 μm range, and equal to or greater than 85 percent in the 1.0–3.0 μm range when tested in accordance with AHRI Standard 680.
p.476D. Air filter pressure drop. All systems shall be provided with air filters that conform to the
p.476applicable maximum allowable clean-filter pressure drop specified in Subsection i, ii, iii or iv below, when tested using ASHRAE Standard 52.2, or as rated using AHRI Standard 680, for the applicable design airflow rates for the system air filters.
p.476i. The maximum allowable clean-filter pressure drop shall be determined by the system
p.476design for the nominal two-inch minimum depth air filter required by Section 160.2(b)1Biia, or
p.476ii. A maximum of 25 Pa (0.1 inches water) clean-filter pressure drop shall be allowed for a
p.476nominal 1-inch depth air filter sized according to Section 160.2(b)1Biib, orp.477
p.476SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
p.477iii. For systems specified in Sections 160.2(b)1Aii and 160.2(b)1Aiii, the maximum
p.477allowable clean filter pressure drop shall be determined by the system design.
p.477iv. If Exception 1 to Section 160.3(b)5Lii or iv is utilized for compliance with cooling system
p.477airflow rate and fan efficacy requirements, the clean-filter pressure drop for the system air filter shall conform to the requirements given in Table 160.3-A or 160.3-B.
p.477E. Air filter product labeling. Systems described in Section 160.2(b)1Ai shall be equipped with
p.477air filters that have been labeled by the manufacturer to disclose the efficiency and pressure drop ratings that demonstrate conformance with Sections 160.2(b)1C and 160.2(b)1D.
p.4772. Ventilation and indoor air quality for attached dwelling units. All attached dwelling units shall meet the requirements of ASHRAE Standard 62.2, Ventilation and Acceptable Indoor Air Quality in Residential Buildings subject to the amendments specified in Section 160.2(b)2A below. All dwelling units shall comply with Section 160.2(b)2B below.
p.477A. Amendments to ASHRAE 62.2 requirements.
p.477i. Window operation. Window operation is not a permissible method of providing the
p.477dwelling unit ventilation airflow specified in Subsection iv or v below.
p.477ii. Central fan integrated (CFI) ventilation systems.
p.477a. Continuous operation prohibition. Continuous operation of a dwelling unit's central
p.477forced air system air handlers used in CFI ventilation systems is not a permissible method of providing the whole-dwelling unit ventilation airflow required by Section 160.2(b)2Aiv.
p.477b. Outdoor air damper(s). A motorized damper(s) shall be installed on the connected
p.477ventilation duct(s) of CFI systems that prevents all airflow into or out of the space- conditioning duct system when the damper(s) is closed.
p.477c. Damper control. The required motorized damper(s) shall be controlled to be in an
p.477opened position when outdoor air ventilation is required for compliance, and shall be in the closed position when ventilation air is not required. The damper(s) shall be closed whenever the space-conditioning system air handling unit is not operating. If the outdoor airflow for the CFI ventilation system is fan-powered, then the outdoorp.478
p.477SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
p.478air fan shall not operate when the required motorized damper(s) on the outdoor air ventilation duct(s) is closed.
p.478d. Variable ventilation. CFI ventilation systems shall incorporate controls that track
p.478outdoor air ventilation run time, and either open or close the required motorized damper(s) depending on whether or not outdoor air ventilation is required for compliance with Section 160.2(b)2Aiv. During periods when comfort conditioning is not called for by the space-conditioning thermostat, the CFI ventilation system controls shall operate the space-conditioning system central fan and outdoor air damper(s) when necessary to ensure compliance with the minimum outdoor air ventilation required by Section 160.2(b)2Aiv in accordance with applicable variable mechanical ventilation methods specified in ASHRAE 62.2 Section 4.5.
p.478iii. Air filtration. Air filtration shall conform to the specifications in Section 160.2(b)1.
p.478Compliance with ASHRAE 62.2 Sections 6.7 (Minimum Filtration) and 6.7.1 (Filter Pressure Drop) shall not be required.
p.478iv. Whole-dwelling unit mechanical ventilation. Multifamily attached dwelling units shall
p.478comply with Subsections a and b below.
p.478a. Mechanical ventilation airflow shall be provided at rates greater than or equal to
p.478the value determined in accordance with Equation 160.2-B.
p.478Total Required Ventilation Rate [ASHRAE 62.2:4.1.1].
Equation text: Qtot = 0.03Afloor + 7.5(Nbr + 1) (Equation 160.2-B)
Needs visual review
p.478Qtot = total required ventilation rate, cfm
p.478Afloor = dwelling-unit floor area, ft
p.478Nbr = number of bedrooms (not to be less than 1)
p.478b. All dwelling units in a multifamily building shall use the same whole-dwelling unit
p.478ventilation system type. The dwelling unit shall comply with Subsections 1 and 2 below.
p.4781. Balanced or supply ventilation. A balanced or supply ventilation system shall provide the required whole-dwelling-unit ventilation airflow. Balanced systems with heat recovery or energy recovery that serve a single dwelling unit shall have a fan efficacy of ≤1.0 W/cfm; and
p.4782. Compartmentalization Testing. The air leakage rate shall not exceed 0.3 cubic feet per minute at 50 Pa (0.2 inch water) per ft2 of dwelling unit envelope surface area as confirmed by ECC-rater field verification and diagnostic testing in accordance with the procedures specified in Reference Appendix RA3.8 or NA2.3 as applicable. In multifamily buildings with four or more habitable stories, the field verification and diagnostic testing which requires an ECC-Rater mayp.479
p.478SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
p.479alternatively be performed by a certified Mechanical Acceptance Test Technician according to the requirements specified in Reference Appendix NA1.9.
p.479v. Multifamily building central ventilation system airflow rate tolerance. Multifamily
p.479building central ventilation systems that serve multiple dwelling units shall have airflow rates in each dwelling unit served that meet or exceed a design ventilation airflow rate specification.
p.479a. Designers shall specify a design ventilation airflow rate for each dwelling unit that is
p.479equal to or greater than the rate specified by Equation 160.2-B.
p.479b. The design ventilation airflow rate for each dwelling unit shall be stated on the
p.479building design plans approved by the enforcement agency.
p.479c. Airflow in each dwelling unit shall be no more than twenty percent greater than the
p.479specified design ventilation airflow rate. Ventilation systems shall utilize mechanical or software airflow control means to ensure each of the dwelling-unit airflows can be maintained at the design ventilation airflow within this tolerance at all times. System airflow control-means may include but are not limited to constant air regulation devices, orifice plates and variable speed central fans.
p.479vi. Local mechanical exhaust. A local mechanical exhaust system shall be installed in each
p.479kitchen and bathroom. Systems shall be rated for airflow in accordance with ASHRAE 62.2 Section 7.1.
p.479a. Nonenclosed kitchens shall have a demand-controlled mechanical exhaust system
p.479meeting the requirements of Section 160.2(b)2Avic.
p.479b. Enclosed kitchens and all bathrooms shall have either one of the following options
p.4791 or 2:
p.4791. A demand-controlled mechanical exhaust system meeting the requirements of Section 160.2(b)2Avic; or
p.4792. A continuous mechanical exhaust system meeting the requirements of Section 160.2(b)2Avid.
p.479c. Demand-controlled mechanical exhaust. A local mechanical exhaust system shall
p.479be designed to be operated as needed.
p.4791. Control and operation. Demand-controlled mechanical exhaust systems shall be provided with at least one of the following controls:
p.479A. A readily accessible occupant-controlled ON-OFF control.
p.479B. An automatic control that does not impede occupant ON control.
p.4792. Ventilation rate and capture efficiency. The system shall meet or exceed either the minimum airflow in accordance with Table 160.2-E or the minimum capture efficiency in accordance with Table 160.2-E, and Table 160.2-G. Capture efficiency ratings shall be determined in accordance with ASTM E3087, and listed in a product directory approved by the Energy Commission.p.480
p.479SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
p.480d. Continuous mechanical exhaust. A mechanical exhaust system shall be installed to
p.480operate continuously. The system may be part of a balanced mechanical ventilation system.
p.4801. Control and operation. A manual ON-OFF control shall be provided for each continuous mechanical exhaust system. The system shall be designed to operate during all occupiable hours. For multifamily dwelling units, the manual ON-OFF control may be accessible to the dwelling unit occupant; however, the manual ON-OFF control shall not be required to be accessible to the dwelling unit occupant.
p.4802. Ventilation rate. The minimum delivered ventilation shall be at least the amount indicated in Table 160.2-F during each hour of operation.
p.480e. Airflow measurement of local mechanical exhaust by the system installer. The
p.480airflow required by Section 160.2(b)2Avi is the quantity of indoor air exhausted by the ventilation system as installed in the dwelling unit. When a vented range hood utilizes a capture efficiency rating to demonstrate compliance with Section 160.2(b)2Avic2, the airflow listed in the approved directory corresponding to the compliant capture efficiency rating point shall be met by the installed system. The as-installed airflow shall be verified by the system installer to ensure compliance by use of either Subsection 1 or 2 below:
p.4801. The system installer shall measure the airflow by using a flow hood, flow grid or other airflow measuring device at the mechanical ventilation fan’s inlet terminals/grilles or outlet terminals/grilles in accordance with the procedures in Reference Appendix RA3.7 or NA2.2 as applicable.
p.4802. As an alternative to performing an airflow measurement of the system as installed in the dwelling unit, compliance may be demonstrated by installing an exhaust fan and duct system that conforms to the specifications of Table 160.2- H. Visual inspection shall verify the installed system conforms to the requirements of Table 160.2-H.
p.480When using Table 160.2-H for demonstrating compliance, the airflow rating shall be greater than or equal to the value required by Section 160.2(b)2Avi at a static pressure greater than or equal to 0.25 in. of water (62.5 Pa). When a vented range hood utilizes a capture efficiency rating to demonstrate compliance with Section 160.2(b)2Avic2, a static pressure greater than or equal to 0.25 in. of water at the rating point shall not be required, and the airflow listed in the approved directory corresponding to the compliant capture efficiency rating point shall be applied to Table 160.2-H for determining compliance.
p.480Use of Table 160.2-H is limited to ventilation systems that conform to all of the following three specifications:p.481
p.480SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY
p.481A. Total duct length is less than or equal to 25 feet (8 m),
p.481B. Duct system has no more than three elbows, and
p.481C. Duct system has exterior termination fitting with a hydraulic diameter
p.481greater than or equal to the minimum duct diameter and not less than the hydraulic diameter of the fan outlet.
p.481f. Sound ratings for local mechanical exhaust. Local mechanical exhaust systems shall
p.481be rated for sound in accordance with Section 7.3 of ASHRAE 62.2 at no less than the minimum airflow rate required by Section 160.2(b)2Avi.
p.481vii. Airflow measurement of whole-dwelling unit ventilation. The airflow required by
p.481Section 160.2(b)2Aiv or 160.2(b)2Av is the quantity of outdoor ventilation air supplied or indoor air exhausted by the mechanical ventilation system as installed and shall be measured by using a flow hood, flow grid or other airflow measuring device at the mechanical ventilation fan’s inlet terminals/grilles or outlet terminals/grilles in accordance with the procedures in Reference Appendix Section RA3.7.4.1.1 or NA2.2.4.1.1 as applicable for supply and exhaust systems or RA3.7.4.1.2 or NA2.2.4.1.2 as applicable for balanced systems. Balanced mechanical ventilation system airflow shall be the average of the supply fan and exhaust fan flows.
p.481viii. Sound ratings for whole-dwelling unit ventilation systems. Whole-dwelling unit
p.481ventilation systems shall be rated for sound in accordance with Section 7.3 of ASHRAE 62.2 at no less than the minimum airflow rate required by Section 160.2(b)2Aiv or 160.2(b)2Av as applicable.
p.481ix. Label for whole-dwelling unit ventilation system on-off control. Compliance with
p.481ASHRAE 62.2 Section 4.4 (Control and Operation) shall require manual ON-OFF control switches associated with whole-dwelling unit ventilation systems to have a label clearly displaying the following text, or equivalent text: “This switch controls the indoor air quality ventilation for the home. Leave switch in the ‘on’ position at all times unless the outdoor air quality is very poor.”
p.481x. Combustion air and compensating outdoor air or makeup air.
p.481a. All dwelling units shall conform to the applicable requirements specified in California Mechanical Code Chapter 7, Combustion Air.
p.481b. All dwelling units shall conform to the requirements in ASHRAE 62.2 Section 6.4,
p.481Combustion and Solid-Fuel-Burning Appliances.
p.481xi. Balanced and supply ventilation component accessibility. Balanced and supply
p.481ventilation systems shall meet the following requirements for accessibility:
p.481a. IAQ filter and HRV/ERV accessibility. System air filters and HRV/ERV heat/energy
p.481recovery cores shall be located such that they are accessible for service from within occupiable spaces, basements, garages, balconies, mechanical closets or accessible rooftops. Filters and heat/energy recovery cores behind access panels, access doors,p.482
p.481SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY

Text in this table
SECTION 160.2 – MANDATORY REQUIREMENTS FOR VENTILATION AND INDOOR AIR QUALITY or grilles located no more than 10 feet above a walking surface inside a space specified above comply with this requirement. Exception to Section 160.2(b)2Axia: Systems that require servicing from inside the attic shall have the following: 1. A Fault Indicator Display (FID) meeting the requirements of Reference Appendix JA 17; and 2. An attic access door located in a wall or, where attic access is provided through a ceiling, an attic access hatch that includes an integrated ladder; and 3. A walkway from the attic access door to the HRV/ERV. b. IAQ system component accessibility. Fans, motors, heat exchangers, filters and recovery cores shall meet all applicable requirements of California Mechanical Code 304.0 accessibility of service. B. Dwelling unit field verification and diagnostic testing. i. The whole-dwelling unit ventilation airflow required by Section 160.2(b)2Aiv or 160.2(b)2Av shall be confirmed through field verification and diagnostic testing in accordance with Reference Appendix RA3.7.4.1.1 or NA2.2.4.1.1 as applicable for supply and exhaust systems or RA3.7.4.1.2 or NA2.2.4.1.2 as applicable for balanced systems. Balanced mechanical ventilation system airflow shall be the average of the supply fan and exhaust fan flows. Ventilation airflow of systems with multiple operating modes shall be tested in all modes designed to comply with the required ventilation airflows. ii. Kitchen local mechanical exhaust—vented range hoods. Vented range hoods installed to comply with local mechanical exhaust requirements specified in Section 160.2(b)2Avi shall be field verified in accordance with Reference Appendix RA3.7.4.3 or NA2.2.4.1.4 as applicable to confirm the model is rated by HVI or AHAM to comply with the following requirements: a. The minimum ventilation airflow rate as specified by Section 160.2(b)2Avi, or alternatively the minimum capture efficiency as specified by Section 160.2(b)2Avi; and b. The maximum sound rating as specified in Section 160.2(b)2Avif. iii. Heat recovery ventilation (HRV) and energy recovery ventilation (ERV) system fan efficacy. At a minimum, systems with heat or energy recovery serving a single dwelling unit shall have a fan efficacy of ≤1.0 W/cfm as confirmed by field verification in accordance with Reference Appendix RA3.7.4.4 or NA2.2.4.1.5 as applicable. If Section 170.2(c)3Biva requirements are applicable to the dwelling unit, then field verification shall instead confirm compliance with the maximum fan efficacy and minimum sensible recovery efficiency specified in Section 170.2(c)3Biva in accordance with the procedures specified in Reference Appendix RA3.7.4.4 or NA2.2.4.1.5 as applicable.
p.483iv. In multifamily buildings with four or more habitable stories, the field verification and
p.483diagnostic testing required in Sections 160.2(b)2Bi, ii and iii which requires an ECC-Rater may alternatively be performed by a certified Mechanical Acceptance Test Technician according to the requirements specified in Reference Appendix NA1.9.
p.483C. Multifamily building central ventilation system field verification.
p.483i. Central ventilation system duct sealing. Ventilation ducts that conform to Subsections a and b below shall meet the duct sealing requirements in California Mechanical Code Section 603.10 and have leakage that is no greater than six percent of the rooftop fan or central fan design airflow rate as confirmed by field verification in accordance with the procedures in Reference Appendix NA7.18.3. The leakage test shall be conducted using a test pressure of 25 Pa (0.1 inches) for ducts serving six or fewer dwelling units and 50 Pa (0.2 inches) for ducts serving more than six dwelling units, and shall measure the leakage of all ductwork between the central fan and the connection point to the in-unit grille or fan.
p.483a. The ventilation ducts serve multiple dwelling units.
p.483b. The ventilation ducts provide continuous airflows or airflows to provide balanced
p.483ventilation to meet the requirements specified in Section 160.2(b)2Aiv or 160.2(b)2Av as applicable.
p.483(c) Common use areas. All occupiable spaces shall comply with the requirements of Subsection 1 and
p.483shall also comply with either Subsection 2 or Subsection 3: