Section 170.2 – Prescriptive Approach

p.548Section 170.2 – Prescriptive Approach

p.548Multifamily buildings, including both dwelling units and common use areas, that comply with the prescriptive standards shall be designed, constructed and equipped to meet all of the requirements for the appropriate climate zone shown in Table 170.2-A. In Table 170.2-A, NA (not allowed) means that feature is not permitted in a particular climate zone and NR (no requirement) means that there is no prescriptive requirement for that feature in a particular climate zone. Installed components shall meet the following requirements:

p.548(a) Envelope component requirements.

p.5481. Exterior roofs and ceilings. Exterior roofs and ceilings shall comply with each of the applicable requirements in this subsection:

p.548A. Roofing products. All roofing products shall meet the requirements of Section 110.8 and the

p.548applicable minimum aged solar reflectance and thermal emittance requirements of Table 170.2-A.

p.548B. Roof insulation. Roofs shall have an overall assembly U-factor no greater than the

p.548applicable value in Table 170.2-A, meeting i, ii, iii or iv below. Where required by Sections 110.8 and 160.1(a), insulation shall be placed in direct contact with a continuous roof or drywall ceiling.

p.548i. Option A: Reserved.

p.548ii. Option B: A minimum R-value of insulation installed between the roof rafters in contact

p.548with the roof deck and an additional layer of ceiling insulation located between the attic and the conditioned space when meeting Section 170.2(c)3Biia; or

p.548iii. Option C: A minimum R-value of ceiling insulation located between the attic and the

p.548conditioned space when meeting Section 170.2(c)3Biib.

p.548iv. Option D: A minimum U-factor for roof assemblies above conditioned space without

p.548attic space.

p.548C. Radiant barrier. A radiant barrier required in Table 170.2-A shall meet the requirements

p.548specified in Section 110.8(j) and shall meet the installation criteria specified in Reference Residential Appendix RA4.

p.5482. Wall insulation.

p.548A. Exterior walls shall have an overall assembly U-factor no greater than the applicable value

p.548in Table 170.2-A.

p.548SECTION 170.2 – PRESCRIPTIVE APPROACH

p.549B. Demising walls shall meet the requirements of Section 160.1(b)7. Vertical windows in

p.549demising walls between conditioned and unconditioned spaces shall have an area-weighted average U-factor no greater than the applicable value in Table 170.2-A.