p.614Section 180.1 – Additions Additions to existing multifamily buildings shall meet the applicable requirements of Sections 110.0 through 110.9; Sections 160.0, 160.1, and 160.2(c) and (d); Sections 160.3 through 160.7; and either Section 180.1(a) or 180.1(b).
p.614(a) Prescriptive approach. The envelope and lighting of the addition; any newly installed space-
p.614conditioning or ventilation system, electrical power distribution system, or water-heating system; any addition to an outdoor lighting system; and any new sign installed in conjunction with an indoor or outdoor addition shall meet the applicable requirements of Sections 110.0 through 110.12; 160.0, 160.1, and 160.2(c) and (d); and 160.3 through 170.2.
p.614A. Additions that are greater than 700 square feet shall meet the requirements of
p.614Section 170.2(a), with the following modifications:
p.614i. Framed walls extension. Extensions of existing wood-framed walls may retain the
p.614dimensions of the existing walls and shall install cavity insulation of R-15 in a 2x4 framing and R-21 in a 2x6 framing.
p.614ii. The maximum allowed fenestration area shall be the greater of 175 square feet
p.614or 20 percent of the addition floor area.
p.614iii. When existing siding of a wood-framed wall is not being removed or replaced,
p.614cavity insulation of R-15 in a 2x4 framing and R-21 in a 2x6 framing shall be installed and continuous insulation is not required.p.615
p.614SECTION 180.1 – ADDITIONS
p.6152025 Building Energy Efficiency Standards
p.615iv. Additions that consist of the conversion of existing spaces from unconditioned to
p.615conditioned space shall not be required to perform the air sealing part of QII when the existing air barrier is not being removed or replaced.
p.615B. Additions that are 700 square feet or less shall meet the requirements of Section
p.615170.2(a), with the following modifications.
p.615i. Roof and ceiling insulation in a ventilated attic shall meet one of the following
p.615requirements: a. In Climate Zones 1, 2, 4, and 8 through 16, achieve an overall assembly U-
p.615factor not exceeding 0.025. In wood framed assemblies, compliance with U- factors may be demonstrated by installing insulation with an R-value of R-38 or greater.
p.615b. In Climate Zones 3 and 5 through 7, achieve an overall assembly U-factor not
p.615exceeding 0.031. In wood framed assemblies, compliance with U-factors may be demonstrated by installing insulation with an R-value of R-30 or greater.
p.615ii. Radiant barrier. For buildings three habitable stories or less, radiant barriers shall
p.615be installed in attics with exposed attic deck undersides in Climate Zones 2–15.
p.615iii. Extensions of existing wood-framed walls may retain the dimensions of the
p.615existing walls and shall install cavity insulation of R-15 in a 2x4 framing and R-21 in a 2x6 framing; and
p.615iv. Fenestration products must meet the U-factor, RSGHC and VT requirements of
p.615v. Quality Insulation Installation (QII) requirements of Section 170.2(a)6 do not
p.615apply.
p.6152. Mechanical ventilation for indoor air quality. Additions to existing buildings shall comply with Section 160.2 subject to the requirements specified in Subsections A and B below. When field verification and diagnostic testing are required by Section 180.1(a)2, buildings with three habitable stories or less shall use the applicable procedures in the Residential Appendices, and buildings with four or more habitable stories shall use the applicable procedures in Nonresidential Appendices NA1 and NA2.