p.520Section 160.5 – Mandatory Lighting Requirements for Indoor and Outdoor Spaces
p.520The design and installation of all lighting systems and equipment in multifamily buildings within the scope of Section 100.0(a) shall comply with the applicable provisions of Section 160.5. All functional areas except dwelling units and common living areas shall comply with the applicable requirements of Sections 160.5(b) through 160.5(e).
p.520(a) Dwelling unit lighting.
p.520The design and installation of all lighting systems and equipment in multifamily dwelling units shall comply with Section 160.5(a). Multifamily dwelling units include dormitory and senior housing dwelling accommodations. Outdoor lighting attached to multifamily buildings and controlled from the inside of a dwelling unit shall comply with the lighting requirements of Section 160.5(a).
p.5201. Luminaire requirements
p.520A. Luminaire efficacy. All installed luminaires and light sources shall comply with Reference
p.520Joint Appendix JA8 and shall be certified and marked as required by JA8. Exception 1 to Section 160.5(a)1A: Integrated device lighting: Lighting integral to exhaust fans, kitchen range hoods, bath vanity mirrors, garage door openers, and ceiling fan kits that are subject to DOE's Appliance and Equipment Standards Program.
p.520i. LED light sources installed outdoors;
p.520ii. inseparable solid state lighting (SSL) luminaires containing colored light sources that are
p.520installed to provide decorative lighting;
p.520iii. High intensity discharge (HID) light sources, including pulse start metal halide and high
p.520pressure sodium light sources; and iv. Luminaires with hardwired high frequency generator and induction lamp.
p.520C. Recessed downlight luminaires. In addition to complying with Section 160.5(a)1A,
p.520luminaires recessed into ceilings shall meet all of the following requirements:
p.520i. Shall not contain screw base lamp sockets; and
p.520ii. Have a label that certifies the luminaire is airtight with air leakage less than 2.0 cfm at
p.52075 Pascals when tested in accordance with ASTM E283. An exhaust fan housing with integral light shall not be required to be certified airtight; and
p.520SECTION 160.5 – MANDATORY LIGHTING REQUIREMENTS FOR INDOOR AND OUTDOOR SPACES
p.521iii. Be sealed with a gasket or caulk between the luminaire housing and ceiling, and have all
p.521air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk, or be installed per manufacturer’s instructions to maintain airtightness between the luminaire housing and ceiling; and