| Table RA3.1-1 – Summary | of Duct System Field Verification and Diagnostic Test | Protocols | |
|---|---|---|---|
| Verification/Diagnostic | Description | Procedure | |
| Duct Location, Surface Area and R-value | Verify duct system was installed according to the specifications on the Certificate of Compliance or in accordance with an approved duct system design layout. | RA3.1.4.1 | |
| Verified Duct System Design | Procedure for duct system design layout approval and field verification | RA3.1.4.1.1 | |
| Duct Leakage | Verify that duct leakage is less than or equal to the compliance criteria given in Table RA3.1-2. | RA3.1.4.3 | |
| Return Duct Design | Verify compliance with the return duct and return grill sizing requirements of Table 150.0-B or Table 150.0-C). | RA3.1.4.4 | |
| Air Filter Device Design | Verify compliance with the requirements in 150(m) 12. | RA3.1.4.5 | |
| Verification of Prescriptive Bypass Duct Requirements | Verification to confirm zonally controlled systems comply with the bypass duct requirements in 150.1(c) 13 | RA3.1.4.6 | |
| Verification of Space- Conditioning System Airflow Supply to All Habitable Spaces | Verify that all habitable spaces in the dwelling unit receive space-conditioning system airflow. | RA3.1.4.1.7 | |
| Verification of Ductless Space-Conditioning System Indoor Units Located Entirely in Conditioned Space | Verify that ductless indoor units are located entirely in conditioned space. | RA3.1.4.1.8 |
p.324RA3.1.2 Instrumentation Specifications
p.324The instrumentation for the air distribution diagnostic measurements shall conform to the following specifications:
p.324RA3.1.2.1 Pressure Measurements
p.324All pressure measurements shall be measured with measurement systems (i.e. sensor plus data acquisition system) having an accuracy equal to or better than ± 1% of pressure reading or ± 0.2 Pa. (0.0008 inches water) (whichever is greater). All pressure measurements within the duct system shall be made with static pressure probes such as Dwyer A303 or equivalent.
p.324Appendix RA3– Residential Field Verification and Diagnostic Test Protocolsp.325
p.3252025 Residential Appendices RA3.1.2.2 Duct Leakage Measurements