RA3.1.2.2 Duct Leakage Measurements

p.3252025 Residential Appendices RA3.1.2.2 Duct Leakage Measurements

p.325Duct leakage airflow rates during duct leakage testing shall be measured with a duct leakage airflow rate measurement apparatus that has a duct leakage airflow rate measurement accuracy equal to or better than ± 3 percent of reading or ± 1 cfm (whichever is greater).

p.325RA3.1.2.3 Calibration

p.325All instrumentation used for duct leakage diagnostic measurements shall be calibrated according to the manufacturer’s calibration procedure to conform to the accuracy requirement specified in Section RA3.1.2.

p.325RA3.1.3 Diagnostic Apparatus

p.325RA3.1.3.1 Apparatus for Duct Pressurization and Leakage Flow Measurement

p.325The apparatus for fan pressurization duct leakage measurements shall consist of a duct pressurization and flow measurement device meeting the specifications in Section RA3.1.2.

p.325RA3.1.3.2 Apparatus for Duct Leakage to Outside Measurement

p.325The apparatus for measuring duct leakage to outside shall include a fan that is capable of maintaining the pressure within the conditioned spaces in the house at 25 Pa (0.1 inches water) relative to the outdoors. The fan most commonly used for this purpose is known as a “blower door” and is typically installed within a temporary seal of an open exterior doorway.

p.325RA3.1.3.3 Apparatus for Smoke-Test of Accessible-Duct Sealing (Existing Duct Systems)

p.325The apparatus for determining leakage in and verifying sealing of all accessible leaks in existing duct systems provide means for introducing controllable amounts of non-toxic visual/theatrical smoke into the duct pressurization apparatus for identifying leaks in accessible portions of the duct system. The means for generating smoke shall have sufficient capacity to ensure that any accessible leaks will emit visibly identifiable smoke.

p.325RA3.1.4 Verification and Diagnostic Procedures

p.325This section describes the procedures used to verify compliance with the mandatory and performance compliance requirements for air distribution systems.

p.325RA3.1.4.1 Diagnostic Duct Location, Surface Area and R-value

p.325The performance compliance calculations allow credit for duct systems that are designed to be in advantageous locations, that have reduced duct surface areas, and/or that provide higher R- values or portions of the system. This section specifies procedures for verification of duct systems for conformance with the requirements for the performance compliance credits. When indicated on the Certificate of Compliance, the Installer shall certify compliance with the applicable procedures in RA3.1.4.1 on a Certificate of Installation, and an ECC-rater shall verify compliance on a Certificate of Verification.

p.325Appendix RA3– Residential Field Verification and Diagnostic Test Protocols