p.4462025 Residential Appendices RA4.2.1.1 For Prescriptive Compliance: The attic shall be ventilated to:
p.446(a) Provide a minimum free ventilation area of not less than one square foot of vent area for
p.446each 300 ft2 of attic floor area.
p.446(b) Provide no less than 30 percent upper vents.
p.446(c) Ridge vents or gable end vents are recommended to achieve the best performance. The
p.446material should be cut to allow for full airflow to the venting.
p.446(d) The product shall meet all requirements for California certified insulation materials [radiant
p.446barriers] of the Department of Consumer Affairs, Bureau of Household Goods and Services, as specified by CCR, Title 24, Part 12, Chapter 12-13, Standards for Insulating Material.
p.446(e) The use of a radiant barrier shall be listed in the Special Features and Modeling Assumptions
p.446listings of the Certificate of Compliance and described in detail in the Residential ACM Manual Conform to the radiant barrier manufacturer's instructions.
p.446RA4.2.2 Fenestration Including Dynamic Glazing
p.446For each manufactured fenestration products including dynamic glazing a temporary NFRC Label, or a temporary Default Label, will be attached to each fenestration product. The labels shall remain attached to the fenestration product until the building inspector verifies the efficiencies.
p.446Before installation the installer or responsible party shall fill out the Installation Certificate form for the fenestration including dynamic glazing and verify the efficiencies (e.g., U-factor and SHGC) matches the Certificate of Compliance and the building plans. A copy of the Installation Certificate shall remain at the job site and a copy given to the building owner and the enforcement agency for their records.
p.446RA4.2.2.1 Installer Shall Verify:
p.446(a) Name of the manufacture, brand name, model matches building plans or energy compliance
p.446forms;
p.446(b) That each manufactured fenestration product shall be provided with a temporary NFRC Label
p.446Certificate or a Default Label to identify the thermal performance (e.g., U-factor, and SHGC) of each fenestration product being installed;
p.446(c) Identify the azimuth orientation in degrees or in cardinal orientation for each of the installed
p.446fenestration products and annotated on the Installation Certificate;
p.446(d) If no NFRC Label is included on the fenestration, then verify with the Responsible Person of
p.446the building construction or enforcement agency to ensure the fenestration product used actually meets or exceeds the energy specifications;
p.446(e) For dynamic glazing, to ensure reliable proper control operation, the controls shall be
p.446installed and verified to meet manufactures operation specifications. A copy of the User Manual shall be provided to the building owner;
p.446(f) The installer completes and signs the Declaration Statement on the Installation Certificate
p.446and signed copy of the Installation Certificate(s) shall remain at the job site; and
p.446– Eligibility Criteria for Energy Efficiency Measures