p.5562025 Nonresidential Appendices
| Table | NA-7 RECIRCULATING WATER PARAMETERS | ||
|---|---|---|---|
| Recirculating Water Parameters | Maximum Values | ||
| Conductivity (micro-siemens/cm) | 2970 micro-siemens/cm | ||
| Total dissolved solids (ppm) | 1845 ppm | ||
| Total alkalinity as CaCO23 (ppm) excluding galvanized steel | 540 ppm | ||
| Total alkalinity as CaCO3 (ppm) galvanized steel (passivated) | 450 ppm | ||
| Calcium hardness as CACO3 (ppm) | 540 ppm | ||
| Chlorides as Cl (ppm) | 270 ppm | ||
| Sulfates (ppm) | 225 ppm | ||
| Silica (ppm) | 135 ppm | ||
| Langelier saturation index (LSI) | 2.5 LSI |
p.556NA7.5.18.2 Functional Testing
p.556Step 1: Override the makeup water valve to open until the tower water is above the
p.556maximum fill level.
p.556Step 2: Close the makeup water valve. Verify that the overflow alarm is triggered either
p.556through an audible signal or via alert to the Energy Management Control System.
p.556Step 3: Restore the makeup water control parameter to automatic control.
p.556Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes