NA7.5.18.2 Functional Testing

p.5562025 Nonresidential Appendices

TableNA-7 RECIRCULATING WATER PARAMETERS
Recirculating Water ParametersMaximum Values
Conductivity (micro-siemens/cm)2970 micro-siemens/cm
Total dissolved solids (ppm)1845 ppm
Total alkalinity as CaCO23 (ppm) excluding galvanized steel540 ppm
Total alkalinity as CaCO3 (ppm) galvanized steel (passivated)450 ppm
Calcium hardness as CACO3 (ppm)540 ppm
Chlorides as Cl (ppm)270 ppm
Sulfates (ppm)225 ppm
Silica (ppm)135 ppm
Langelier saturation index (LSI)2.5 LSI

p.556NA7.5.18.2 Functional Testing

p.556Step 1: Override the makeup water valve to open until the tower water is above the

p.556maximum fill level.

p.556Step 2: Close the makeup water valve. Verify that the overflow alarm is triggered either

p.556through an audible signal or via alert to the Energy Management Control System.

p.556Step 3: Restore the makeup water control parameter to automatic control.

p.556Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes