JA5.2.5 User Display and Interface

p.173(a) A Demand Response Signal shall trigger the OCST to adjust the thermostat

p.173setpoint by either the default number of degrees or the number of degrees established by the occupant.

p.173(b) When a price signal indicates a price in excess of a price threshold established by

p.173the occupant, the OCST shall adjust the thermostat setpoint by either the default number of degrees or the number of degrees established by the occupant.

p.173(c) In response to price signals or Demand Response signals, the OCST shall default

p.173to an event response that initiates setpoint offsets of +4°F for cooling and -4°F for heating relative to the current setpoint.

p.173(d) The OCST shall have the capability to allow occupants or their representative to

p.173modify the default event response with occupant defined event responses for cooling and heating relative to the current setpoint in response to price signals or Demand Response Signals.

p.173(e) Override Function: Occupants shall be able to change the event responses and

p.173thermostat settings or setpoints at any time, including during price events or Demand Response Periods.

p.173(f) The Demand Response Signal shall start the Demand Response Period either

p.173immediately or at a specific start time as specified in the event signal and continue for the Demand Response Period specified in the Demand Response Signal or until the occupant overrides the event setpoint.

p.173(g) The thermostat’s price response shall start either immediately or at a specific start

p.173time as specified in the pricing signal and continue for the duration specified in the pricing signal or until the occupant overrides the event setpoint.

p.173(h) The OCST shall have the capability to allow occupants to define setpoints for

p.173cooling and heating in response to price signals or Demand Response signals as an alternative to the default event response.

p.173(i) At the end of a price event or Demand Response Period, the thermostat setpoint

p.173shall be set to the setpoint that is programmed for the point in time that the event ends or to the manually established setpoint that existed just prior to the Demand Response Period.

p.173The OCST shall include the capability to allow the occupant to restore the factory installed default settings.

p.173JA5.2.5 User Display and Interface The OCST shall have the capability to display information to the user. The following information shall be readily available whenever the OCST display is active:

p.173(a) communications system connection status,

p.173(b) an indication that a Demand Response Period or pricing event is in progress,

p.173(c) the currently sensed temperature,

p.173(d) the current setpoint.

p.173Appendix JA5 – Technical Specifications for Demand Responsive Thermostats