| For more advanced assemblies, and Building Code Compliance software buildings, the Energy Commission ASHRAE procedures in order to help U-factors of wood and metal framed speed. The output forms of this nonresidential building permit submittal. Table 4.1.1 U-Factor Calculations for steel framed (CBECC) for has developed the building assemblies program can be for Wood Framed | assemblies, both residential an assembly community in with a higher degree used as part of a Assembly | within the California and nonresidential calculator to automate calculating R-values and of accuracy and residential or | |
| Assembly Type: Wall 2x4 16 in. o.c | R-Value | R-Value | |
| Framing Material: WoodA | - | - | |
| Assembly Components | Cavity (Rc) | Frame (Rf) | |
| Outside air film | 0.17 | 0.17 | |
| 3/8 inch 2-coat stucco | 0.08 | 0.08 | |
| 1 inch, R-4 EPS insulating sheathing | 4.0 | 4.0 | |
| Building paper (felt) | 0.06 | 0.06 | |
| R-15 insulation | 15 | - | |
| 2x4 inch doug fir framing @ R 0.99 per inch | - | 3.47 | |
| 0.50 inch gypsum board | 0.45 | 0.45 | |
| Inside air film | 0.68 | 0.68 | |
| Subtotal | 20.44 | 8.91 |
p.85[ 1/Rc x (1 – (Frame% / 100)) ] + [ (1/Rf) x (Frame% / 100) ] = Assembly U-Factor, where: Frame percentage (%) determined by Table 4.1.6
p.85JA4.1.2.2 Accounting for Continuous Insulation R-value
p.85Many of the tables in this appendix have columns for varying levels of continuous insulation. Continuous insulation is insulation that is uninterrupted by framing and provides a continuous insulating layer. Limits on the position of the continuous insulation and other factors are specified in each table. When data from a table is used manually, the R-value of the continuous insulation in the proposed construction shall be equal to or greater than the R-value shown in the column heading; no interpolation is permitted. California Energy Commission approved software used for performance or prescriptive calculations may account for any amount of continuous insulation using Equation 4-1. This adjustment may not be used, however, for continuous insulation with thermal resistance less than R-2.
Equation text: 1 With.Cont.Insul U = 1 + RCont.Insul Col.A U Where:
Needs visual review
p.85Appendix JA4 – U-factor, C-factor, and Thermal Mass Data