p.4422025 Residential Appendices (a) Open the window(s) that are typically opened during WHF operation.
p.442(b) Turn on all WHFs required to meet the dwelling unit WHF airflow rate. Adjust multiple or
p.442variable speed WHFs to operate at an airflow rate that will be greater than or equal to the rate required for compliance.
p.442(c) Adjust the dwelling unit window openings to bring the dwelling unit to the WHF-OP of
p.442negative 10 Pa ± 5 Pa WRT outside.
p.442(d) Measure the airflow rate(s) at the inlet grille(s) in accordance with RA3.9.3.2 with a
p.442calibrated powered flow hood to determine the total WHF airflow for the dwelling unit.
p.442No part of the WHF intake shall be blocked or masked off to accommodate an undersized hood.
p.442Operation of the powered flow hood shall conform to the specifications in the manufacturer's product documentation.
p.442RA3.9.4.1.3 WHF Airflow Rate Measurement Using Traditional Flow Capture Hood
p.442The WHF airflow measurement shall be performed using the following procedures.
p.442(a) Open the window(s) that are typically opened during WHF operation.
p.442(b) Turn on all WHFs required to meet the dwelling unit WHF airflow rate. Adjust multiple or
p.442variable speed WHFs to operate at an airflow rate that will be greater than or equal to the rate required for compliance.
p.442(c) Adjust the dwelling unit window openings to bring the dwelling unit to the WHF-OP of
p.442negative 10 Pa ± 5 Pa WRT outside.
p.442(d) Measure the airflow rate(s) at the inlet grille(s) with a calibrated traditional flow capture
p.442hood to determine the total WHF airflow for the dwelling unit.
p.442No part of the WHF intake shall be blocked or masked off to accommodate an undersized hood.
p.442Operation of the flow hood shall conform to the specifications in the manufacturer's product documentation.
p.442RA3.9.4.2 WHF Fan Watt Draw Measurement Procedures
p.442When multiple WHFs are used to comply with the required WHF watt draw for the dwelling unit, all WHFs in the dwelling unit shall be operated simultaneously and the sum of the watt draw measurements of the simultaneously operating WHFs for the dwelling shall be determined.
p.442When required for compliance, the WHF watt draw shall be measured using one of the following methods:
p.442RA3.9.4.2.1 WHF Watt Draw Measurement Using Portable Watt Meter
p.442The WHF watt draw measurement shall be performed using the following procedures.
p.442(a) The WHF(s) shall be operating at the WHF-OP used for the airflow rate measurement
p.442procedures specified in Section RA3.9.4.1.
p.442(b) Measure the watt draw(s) to determine the total WHF watt draw for the dwelling unit.
p.442– Residential Field Verification and Diagnostic Test Protocols