p.4412025 Residential Appendices WHF airflow shall be measured with the dwelling unit window openings configured such that when the WHF(s) are operating, a dwelling unit pressure of negative 10 Pa ± 5 Pa with reference to (WRT) outside is attained. This is the WHF operating pressure (WHF-OP).
p.441RA3.9.4.1.1 WHF Airflow Rate Measurement Using Attic Pressure Matching and Fan Flowmeter
p.441(a) Open the window(s) that are typically opened during WHF operation.
p.441(b) Place a pressure sensing probe/tube in the attic. If necessary, use a suitable means such
p.441as cardboard sheets and tape to facilitate sealing off the access opening between the attic and the dwelling unit's conditioned space to allow the pressure sensing probe/tube to be inserted into the attic space without crimping or restricting the pressure sensing probe/tube. There shall be no leakage of air from the attic through the attic access opening into the dwelling unit during this verification procedure.
p.441(c) Attach the attic pressure sensing tube to a digital pressure gage such that it will measure
p.441the pressure difference between the dwelling unit conditioned space and the attic.
p.441(d) Turn on all WHFs required to meet the dwelling unit WHF airflow rate required for
p.441compliance. If applicable, adjust multiple WHFs or variable speed WHFs to operate at a total airflow rate greater than or equal to the WHF airflow rate required for compliance.
p.441(e) Adjust the dwelling unit window openings to bring the dwelling unit to the WHF-OP of
p.441negative 10 Pa ± 5 Pa WRT outside.
p.441(f) Measure and record the pressure difference (Pa) between the attic and the dwelling unit
p.441conditioned space (Pattic) while the dwelling unit is at the WHF-OP.
p.441(g) Turn off the WHF.
p.441(h) Do not change the window openings. The same dwelling unit window opening
p.441configuration used to establish the WHF-OP used for the measurement in step (f) shall be used for the pressure matching procedure specified below.
p.441(i) Attach the fan flowmeter to the inlet grille of the WHF. The fan flowmeter's capture
p.441enclosure or ductwork shall cover the WHF intake grille completely.
p.441(j) Turn on all WHFs that were used during the measurement in step (f). The speed of the
p.441WHFs shall be the same as used for the measurement in step (f).
p.441(k) Turn on the fan flowmeter. Adjust the fan flowmeter speed until the pressure difference
p.441(Pa) between the attic and the dwelling unit conditioned space matches Pattic determined in step (f).
p.441(l) Record the flow through the fan flowmeter. When multiple WHFs are used to meet the
p.441required airflow, repeat steps (g) through (l) for each WHF, then sum the airflow measurements for all WHFs to arrive at the total WHF airflow for the dwelling unit.
p.441RA3.9.4.1.2 WHF Airflow Rate Measurement Using Powered Flow Capture Hood
p.441The WHF airflow measurement shall be performed using the following procedures:
p.441Appendix RA3– Residential Field Verification and Diagnostic Test Protocols