RA3.9.3.4 WHF Watt Draw Measurement Apparatus

p.4402025 Residential Appendices capture area at least as large as the WHF inlet grille in all dimensions. All WHF dampers shall be in their normal operating position. Measurement(s) shall be taken at the inlet of the WHF.

p.440RA3.9.3.4 WHF Watt Draw Measurement Apparatus

p.440The air handler watt draw shall be measured using one of the following apparatuses.

p.440RA3.9.3.5 Portable Watt Meter

p.440The apparatus for measuring the WHF watt draw shall consist of a wattmeter meeting the applicable instrumentation specifications in RA3.3.1. The measuring device shall be attached to measure the WHF watt draw. All WHF dampers shall be in their normal operating condition.

p.440When required to measure fan watt draw on WHF equipment that is wired directly to an electrical junction box, it is recommended to use portable true power clamp-on meters to provide flexibility for isolating the correct fan wires serving the WHF.

p.440RA3.9.3.6 Utility Revenue Meter

p.440The apparatus for measuring the WHF watt draw shall consist of a utility revenue meter meeting the applicable instrumentation specifications in RA3.9.2.3 and a stopwatch that provides measurements in units of seconds. All WHF dampers and access panels shall be in their normal operating condition.

p.440RA3.9.3.7 Digital Utility Revenue Meter

p.440The apparatus for measuring the WHF watt draw shall consist of a digital utility revenue meter meeting the applicable instrumentation specifications in RA3.3.1 that provides direct digital display of the watt draw. All WHF dampers and access panels shall be in their normal operating condition.

p.440RA3.9.4 Procedures

p.440RA3.9.4.1 WHF Airflow Rate Measurement Procedures

p.440When required for compliance, the installed WHF airflow shall be diagnostically tested using one of the methods specified in this section.

p.440The measured airflow rate shall be expressed in cubic feet per minute of standard air (standard air has a density of 0.075 lb/ft3). When the airflow measurement is made at altitudes significantly different from sea level or at temperatures significantly different from 70°F, the airflow indicated on the device gauge may differ from the standard CFM by as much as 15 percent. Corrections from indicated to standard CFM shall be made using the procedure specified by the airflow measurement device manufacturer.

p.440When multiple WHFs are used to comply with the required WHF airflow rate for the dwelling unit, all WHFs in the dwelling unit shall be operated simultaneously and the sum of the airflow rate measurements of the simultaneously operating WHFs for the dwelling shall be determined.

p.440When flow capture hood devices are used, the capture area shall be at least as large as the WHF inlet grille in all dimensions.

p.440– Residential Field Verification and Diagnostic Test Protocols