p.4172025 Residential Appendices insulated to meet or exceed the wall R-value of the adjacent exterior wall construction as specified on the Certificate of Compliance.
p.417(b) The backside of air permeable insulation exposed to the unconditioned attic space shall be
p.417completely covered with a continuous air barrier.
p.417RA3.5.7.3 Roof/Ceilings
p.417(a) Baffles shall be placed at eaves or soffit vents of vented attics to keep insulation from
p.417blocking eave ventilation and prevent air movement under the insulation. The required net- free ventilation shall be maintained.
p.417(b) Hard covers or draft stops shall be placed over all drop ceiling areas and interior wall cavities
p.417to keep insulation in place and stop air movement. If hard covers or draft stops are missing or incomplete, they shall be completed before insulation is installed.
p.417(c) In traditional framed attics, required eave ventilation shall not be obstructed for conventional
p.417attics – the net free-ventilation area of the eave vent shall be maintained. Eave vent baffles shall be installed to prevent air movement under or into the ceiling insulation of conventional attics.
p.417(d) Insulation shall cover all recessed lighting fixtures. If the fixtures are not rated for zero
p.417clearance insulation contact (IC) and airtight, the fixture shall be removed and/or replaced.
p.417(e) All recessed light fixtures that penetrate the ceiling shall be listed for zero clearance
p.417insulation contact (IC), have a label that certifies it as airtight with leakage less than 2.0 cfm at 75 Pa when tested to ASTM E283, and shall be sealed with gasket or caulk between the light’s housing and the ceiling.
p.417RA3.5.7.3.1 Special Situations--Attics and Cathedral Ceilings
p.417Insulation installed in unvented rafter ceilings or to the underside of unvented roofs with an attic below shall have an R-value conforming to compliance documentation and the air barrier shall be uniform across the transition of roof to wall. The insulation shall be in contact with the air barrier.
p.417RA3.5.7.3.2 Special Situations--HVAC Platform
p.417Insulation shall be placed below any platform or catwalk for HVAC equipment installation and access, as specified on the Certificate of Compliance.
p.417RA3.5.7.3.3 Special Situations--Attic Access
p.417Permanently attach rigid board insulation, batt or blanket insulation, or SIP with the appropriate R-value to the access door using adhesive or mechanical fastener. The bottom of the attic access shall be gasketed to prevent air leakage of conditioned air to the unconditioned attic.
p.417RA3.5.7.4 Raised Floors
p.417SIPs air barrier shall be maintained through use of SIP tape, or sealing and caulking between panels and at all spline joints.
p.417Appendix RA3– Residential Field Verification and Diagnostic Test Protocols