p.4162025 Residential Appendices RA3.5.7.2.3 Special Situations--Kneewalls and Skylight Shafts
p.416(a) Framing for kneewalls and skylight shafts that separate conditioned from unconditioned
p.416space shall be insulated to meet or exceed the wall R-value specified on the Certificate of Compliance, and all other required compliance documentation.
p.416(b) Steel-framed kneewalls and skylight shafts, shall meet or exceed the mandatory minimum
p.416insulation requirements and external surfaces of steel studs shall be covered with insulation unless otherwise specified on the Certificate of Compliance using correct U-factors from Joint Appendix JA4, Table 4.3.4 (or U-factors approved by the Commission Executive Director).
p.416(c) The backside of air permeable insulation exposed to the unconditioned attic space shall be
p.416completely covered with a continuous air barrier.
p.416RA3.5.7.2.4 Special Situations--HVAC/Plumbing Closet
p.416Walls of interior closets for HVAC and/or water heating equipment, which require combustion air venting, shall be insulated to at least the same R-value as the other demising walls (i.e., walls separating conditioned space and attached garage), or as specified on the Certificate of Compliance.
p.416RA3.5.7.2.5 Special Situations--Double Walls and Framed Bump-Outs
p.416(a) Insulation shall fill the entire cavity; or an additional air barrier shall be installed inside the
p.416double wall or bump-out and in contact with the insulation so that the insulation fills the cavity formed with the additional air barrier.
p.416(b) Entire double walls and framed bump-outs shall be airtight.
p.416RA3.5.7.2.6 Special Situations--Structural Bracing, Tie-downs, Steel Structural Framing
p.416(a) Framing and bracing used for structural purposes shall be identified on plan documents with
p.416diagrams and/or design drawings.
p.416(b) Insulation shall be installed in a manner that restricts thermal bridging through the structural
p.416framing assembly.
p.416(c) Insulation shall be applied to fully enclose and/or adhere to all sides and ends of structural
p.416assembly framing.
p.416(d) The structural portions of assemblies shall be airtight.
p.416RA3.5.7.2.7 Special Situations--Window and Door Headers
p.416All single-member window and door headers shall be insulated to a minimum of R-3 for a 2x4 framing, or equivalent width, and a minimum of R-5 for all other assemblies. Insulation is to be placed between the exterior face of the header and inside surface of the finish wall material.
p.416RA3.5.7.2.8 Special Situations—Gable Ends in Unvented Attics
p.416(a) In unvented attic, where insulation is applied directly to the underside of the roof deck,
p.416framing for gable ends that separate the unvented attic from unconditioned space shall be
p.416– Residential Field Verification and Diagnostic Test Protocols