RA3.5.6.2.8 Special Situations--Structural Bracing, Tie-downs, Steel Structural Framing

p.4112025 Residential Appendices RA3.5.6.2.8 Special Situations--Structural Bracing, Tie-downs, Steel Structural Framing

p.411(a) Framing and bracing used for structural purposes shall be identified on plan documents with

p.411diagrams and/or design drawings.

p.411(b) Insulation shall be installed in a manner that restricts thermal bridging through the structural

p.411framing assembly.

p.411(c) Insulation shall be applied to fully enclose and/or adhere to all sides and ends of structural

p.411assembly framing that separate conditioned from unconditioned space.

p.411(d) The structural portions of assemblies shall be air-tight.

p.411RA3.5.6.2.9 Special Situations--Window and Door Headers

p.411(a) All single-member window and door headers shall be insulated to a minimum of R-3 for a 2x4

p.411framing, or equivalent width, and a minimum of R-5 for all other assemblies. Insulation is to be placed between the interior face of the header and inside surface of the interior wall finish.

p.411(b) No header insulation is required for single-member headers that are the same width as the

p.411wall, provided that the entire wall has at least R-2 insulation.

p.411RA3.5.6.2.10 Special Situations--Gable Ends in Unvented Attics

p.411(a) In unvented attics, where insulation is applied directly to the underside of the roof deck,

p.411framing for gable ends that separate the unvented attic from unconditioned space shall be insulated to meet or exceed the wall R-value of the adjacent exterior wall construction as specified on the Certificate of Compliance.

p.411(b) The backside of air permeable insulation exposed to the unconditioned attic space shall be

p.411completely covered with a continuous air barrier.

p.411RA3.5.6.3 Roof/Ceilings

p.411(a) SPF insulation shall be applied to fully adhere to the substrate of the ceiling or roof deck.

p.411(b) SPF insulation shall be applied to fully adhere to the joist and other framing faces to form a

p.411complete air seal within the construction cavity.

p.411(c) SPF insulation shall be spray-applied to fully adhere to and seal around wiring and plumbing.

p.411(d) Hard covers shall be placed over all drop ceiling areas and interior wall cavities to keep

p.411insulation in place and stop air movement. If hard covers, they shall be in place before insulation is installed.

p.411(e) In vented attics, required eave ventilation shall not be obstructed; the net free-ventilation

p.411area of the eave vent shall be maintained.

p.411(f) In unvented attics where SPF is applied directly to the underside of the roof deck, all gable

p.411end areas shall be insulated to the same R-value as the walls and as specified on compliance documentation. It is not necessary to place hard covers over drop ceilings and interior wall cavities in this situation.

p.411Appendix RA3– Residential Field Verification and Diagnostic Test Protocols