RA3.5.6.3.1 Special Situations--Enclosed Rafter Ceilings

p.4122025 Residential Appendices (g) All recessed light fixtures that penetrate the ceiling shall be listed for zero clearance

p.412insulation contact (IC), have a label that certifies it as airtight with leakage less than 2.0 cfm @ 75 Pa when tested to ASTM E283, and shall be sealed with a gasket or caulk between the light's housing and the ceiling.

p.412(h) SPF insulation shall not be applied directly to recessed luminaires unless the recessed

p.412luminaire is rated for SPF insulation contact (SPCL) appropriate for use with polyurethane spray foam in accordance with NEMA LE 7-2015. Recessed light fixtures not rated for SPF insulation contact (SPCL) and insulated with SPF insulation shall be separated from the spray foam by a suitable barrier or box as directed in NEMA LSD 57-2018. In a cathedral ceiling installation, where SPF is applied above the luminaire, but not encasing it with foam, the luminaire shall have a minimum 1/2-inch air space between the two components.

p.412(i) SPF insulation shall be kept away from combustion appliance flues in accordance with flue

p.412manufacturers' installation instructions or labels on the flue for clearance.

p.412RA3.5.6.3.1 Special Situations--Enclosed Rafter Ceilings

p.412SPF insulation installed in unvented rafter ceilings or to the underside of unvented roofs with an attic below shall have an R-value conforming to compliance documentation and the air barrier shall be uniform across the transition of roof to wall. The insulation shall be in contact with the air barrier.

p.412RA3.5.6.3.2 Special Situations--Attics and Cathedral Ceilings

p.412In attics where entry is made for the service of utilities, SPF shall be protected from ignition in accordance with CBC, Part 2, Section 2603, and Part 2.5, Section R316.

p.412RA3.5.6.3.3 Special Situations--HVAC Platform

p.412A minimum of 3 inches of ccSPF insulation or 5.3 inches of ocSPF shall be placed below any platform or cat-walk access ways installed in vented attics for HVAC equipment or other needs. The overall assembly R-value shall meet the required R-values specified in the compliance documentation.

p.412RA3.5.6.3.4 Special Situations--Attic Access

p.412A minimum of 3 inches of ccSPF or 5.3 inches of ocSPF insulation shall be applied to the access door assuring good adhesion to the door surface. Alternatively, permanently attach rigid foam or batt insulation with adhesive or mechanical fastener. The overall assembly R-value shall meet the required values specified in the compliance documentation.

p.412RA3.5.6.4 Raised Floors

p.412(a) SPF insulation shall be spray-applied to fully adhere to the bottom side of the floor sheathing.

p.412(b) SPF insulation shall uniformly cover the cavity side-to-side and end-to-end.

p.412RA3.5.6.4.1 Homes with Floors Over Garage

p.412(a) SPF insulation shall be spray-applied to fully adhere to the bottom side of the floor sheathing.

p.412– Residential Field Verification and Diagnostic Test Protocols