p.4102025 Residential Appendices (d) The backside of air permeable insulation exposed to the unconditioned attic space shall be
p.410completely covered with a continuous air barrier.
p.410(e) The house side of the insulation shall be in contact with the drywall or other wall finish.
p.410(f) Insulation for all kneewall and skylight shafts shall be completely enclosed by vertical and
p.410horizontal framing, including horizontal plates at top and bottom of the insulation.
p.410(g) SPF insulation shall be installed without gaps.
p.410(h) SPF insulation shall be fully adhered and self-supporting so that it will remain in place.
p.410Filling of Framed Assemblies: ccSPF insulation is not required to fill the cavities of framed assemblies provided the installed thickness of insulation conforms to compliance documentation and that the bottom and top plates of vertical framing and both ends of horizontal framing, including band and rim joists, are sprayed to completely fill the cavity adjacent to and in contact with the framing to a distance of 2.0 inches away from the framing for ocSPF insulation, or filled to the thickness meeting ASTM testing as an air barrier.
p.410Filling of Framed Assemblies: ocSPF insulation shall completely fill cavities of 2x4 inch framing or less. Cavities greater than 2x4 inch framing dimensions may be filled to the thickness that meets the required R-value used for compliance provided that the bottom and top plates of vertical framing and both ends of horizontal framing, including band and rim joists, are sprayed to completely fill the cavity adjacent to and in contact with the framing to a distance of 5.5 inches away from the framing for ocSPF insulation, or filled to the thickness meeting ASTM testing as an air barrier.
p.410Air Barrier: ccSPF installed as an air barrier shall be 2.0 inches in thickness. ocSPF installed as an air barrier shall be a minimum of 5.5 inches in thickness. Alternatively, ccSPF and ocSPF insulation shall be installed at a thickness that meets an air permeance no greater than 0.02 L/s-m2 at 75 Pa pressure differential when tested in accordance with ASTM E2178 or ASTM E283.
p.410RA3.5.6.2.6 Special Situations--HVAC/Plumbing Closet
p.410Walls of interior closets for HVAC and/or water heating equipment that require combustion air venting, shall be insulated to at least the same R-value as the other demising walls (i.e., walls separating conditioned space and attached garage), or as specified on the Certificate of Compliance.
p.410RA3.5.6.2.7 Special Situations--Double Walls and Framed Bump-Outs
p.410(a) Insulation shall fill the entire cavity; or an additional air barrier shall be installed inside the
p.410double wall or bump-out and in contact with the insulation so that the insulation fills the cavity formed with the additional air barrier.
p.410(b) Entire double walls and framed bump-outs shall be airtight.
p.410– Residential Field Verification and Diagnostic Test Protocols