p.4072025 Residential Appendices (g) SPF insulation shall be spray-applied to fully adhere to assembly framing, floor and ceiling the
p.407joists, and other framing surfaces within the construction cavity. When multiple layers of SPF material are applied, each foam lift (i.e., spray application) shall have adhesion at substrate and foam interfaces. SPF insulation shall not exhibit areas that:
p.4071. Have voids or gaps in the uniformity of the insulation
p.4072. Are extremely soft or spongy
p.4073. Show the presence of liquid
p.4074. Have blistering between lifts
p.4075. Show differences in coloration of adjacent foam layers
p.4076. Indicate the presence of other materials between lifts
p.407(h) SPF insulation shall be installed in conformance with the manufacturer’s specifications,
p.407recommendations, and temperature/humidity limitations.
p.407(i) Substrates to which SPF insulation is applied shall be secure and free of surface moisture,
p.407frost, grease, oils, dirt, dust, or other contaminants that would adversely affect SPF adhesion.
p.407(j) SPF insulation shall meet all provisions of the CBC Title 24, Parts 2 and 2.5. SPF shall be
p.407separated from occupied spaces by an approved thermal barrier, such as 0.5 inch gypsum wallboard or other approved material, or show equivalence through testing in accordance with CBC, Title 24, Part 2, Section 2603, and Part 2.5, Section R316.
p.407(k) SPF insulation may be used as the air barrier provided it has been tested to conform to the air
p.407barrier performance conditions of the Standards.
p.407RA3.5.6.1.4 R-value Measurement Equipment
p.407(a) The ECC-rater shall measure the installed thickness of insulation in at least 6 random
p.407locations on walls, roof/ceilings, and floors (i.e., 6 measurements per opaque surface type: wall, roof/ceiling, or floor) to ensure minimum thickness levels necessary to meet the R-value specified on the Certificate of Compliance, and all other required compliance documentation. Measurement areas shall include low and high areas of the SPF insulated surface.
p.407(b) Probes for inspection of installed thickness of SPF insulation. The insulation thickness shall be
p.407verified by using a probe, gauge, or device capable of measuring the installed thickness of insulation. A pointed measurement probe or other gauge or device, capable of penetrating the full thickness of the insulation, shall be used having measurements marked by at least one-eighth inch increments. Insulation thickness measurement probes and gauges or devices shall be accurate to within ±1/8 inch and shall be designed and used in a manner to cause minimal damage to the insulation.
p.407RA3.5.6.1.5 Certificates
p.407All provisions of Residential Appendix RA2 shall be met. The Insulation Certificates of Installation shall be signed by the SPF applicator stating that the installation is consistent with the Certificate of Compliance, plans and specifications for which the building permit was issued shall be
p.407Appendix RA3– Residential Field Verification and Diagnostic Test Protocols