RA3.5.5.3.1 Special Situations--Enclosed Rafter Ceilings

p.4032025 Residential Appendices (b) Hard covers or draft stops shall be placed over all drop ceiling areas and interior wall cavities

p.403to keep insulation in place and stop air movement. If hard covers or draft stops are missing or incomplete, they shall be completed before insulation is installed.

p.403(c) Rigid board insulation installed above the roof deck shall be applied to the outer edge of the

p.403plane of the wall top plate.

p.403(d) Insulation shall cover all recessed lighting fixtures. If the fixtures are not rated for insulation

p.403contact (IC) and airtight, the fixtures shall be removed and/or replaced.

p.403(e) All recessed light fixtures that penetrate the ceiling shall be listed for zero clearance

p.403insulation contact (IC), have a label that certifies it as airtight with air leakage less than 2.0 cfm @ 75 Pa when tested to ASTM E283, and shall be sealed with a gasket or caulk between the light's housing and the ceiling.

p.403RA3.5.5.3.1 Special Situations--Enclosed Rafter Ceilings

p.403(a) An air space shall be maintained between the insulation and roof sheathing as specified by

p.403California Building Code Section 1203.2 and R806.2, or as specified by the local building department.

p.403(b) Insulation installed in unvented rafter ceilings or to the underside of unvented roofs with an

p.403attic below shall have an R-value conforming to compliance documentation and the air barrier shall be uniform across the transition of roof to wall. The insulation shall be in contact with the air barrier.

p.403RA3.5.5.3.2 RESERVED

p.403RA3.5.5.3.3 Special Situations--HVAC Platform

p.403Insulation shall be placed below any platform or catwalk for HVAC equipment installation and access.

p.403RA3.5.5.3.4 Special Situations--Attic Access

p.403Permanently attach rigid board insulation or batt or blanket insulation with the appropriate R- value to the access door using adhesive or mechanical fastener. The bottom of the attic access shall be gasketed to prevent air leakage of conditioned air to the unconditioned attic.

p.403RA3.5.5.4 Raised Floors

p.403Rigid board insulation shall be in contact with the air barrier - usually the subfloor.

p.403RA3.5.5.4.1 Homes with Floors Over Garage

p.403(a) Rigid board insulation shall be in contact with the air barrier - usually the subfloor.

p.403(b) On floors that are over garages, or where there is an air space between the insulation and the

p.403subfloor, the rim joist shall be insulated.

p.403Appendix RA3– Residential Field Verification and Diagnostic Test Protocols