RA3.5.5.2.6 Special Situations--HVAC/Plumbing Closet

p.4022025 Residential Appendices RA3.5.5.2.6 Special Situations--HVAC/Plumbing Closet

p.402Walls of interior closets for HVAC and/or water heating equipment, which require combustion air venting, shall be insulated to at least the same R-value as other demising walls (i.e., walls separating conditioned space and attached garage), or as specified on the Certificate of Compliance.

p.402RA3.5.5.2.7 Special Situations--Double Walls and Framed Bump-Outs

p.402(a) Insulation shall fill the entire cavity; or an additional air barrier shall be installed inside the

p.402double wall or bump-out and in contact with the insulation so that the insulation fills the cavity formed with the additional air barrier.

p.402(b) Entire double walls and framed bump-outs shall be air-tight.

p.402RA3.5.5.2.8 Special Situations--Structural Bracing, Tie-downs, Steel Structural Framing

p.402(a) Framing and bracing used for structural purposes shall be identified on plan documents with

p.402diagrams and/or design drawings.

p.402(b) Insulation shall be installed in a manner that restricts thermal bridging through the structural

p.402framing assembly.

p.402(c) Insulation shall be applied to fully enclose and/or adhere to all sides and ends of structural

p.402assembly framing that separate conditioned from unconditioned space.

p.402(d) The structural portions of assemblies shall be air-tight.

p.402RA3.5.5.2.9 Special Situations--Window and Door Headers

p.402(a) All single-member window and door headers shall be insulated to a minimum of R-3 for a 2x4

p.402framing, or equivalent width, and a minimum of R-5 for all other assemblies. Insulation is to be placed between the interior face of the header and inside surface of the interior wall finish wall material.

p.402(b) No header insulation is required for single-member headers that are the same width as the

p.402wall, provided that the entire wall has at least R-2 insulation.

p.402RA3.5.5.2.10 Special Situation--Gable Ends in Unvented Attics

p.402(a) In unvented attics, where insulation is applied directly to the underside of the roof deck,

p.402framing for gable ends that separate the unvented attic from unconditioned space shall be insulated to meet or exceed the wall R-value of the adjacent exterior wall construction as specified on the Certificate of Compliance.

p.402(b) The backside of air permeable insulation exposed to the unconditioned attic space shall be

p.402completely covered with a continuous air barrier.

p.402RA3.5.5.3 Roof/Ceilings

p.402(a) Baffles shall be placed at eaves or soffit vents of vented attics to keep insulation from

p.402blocking eave ventilation and prevent air movement under the insulation. The required net- free ventilation shall be maintained.

p.402– Residential Field Verification and Diagnostic Test Protocols