RA3.5.5.2.1 Narrow-Framed Cavities

p.4012025 Residential Appendices RA3.5.5.2.1 Narrow-Framed Cavities

p.401(a) Non-standard with cavities shall be filled with insulation to snuggly fit into the space, or with

p.401minimally expansive foam sealing material.

p.401(b) Narrow spaces less than 1 inch in width at windows and door jambs, shall be filled with

p.401minimally expansive foam sealing material. In cases where the manufacturer's warranty would be void if minimally expanding foam is used to seal the gap between the window frame or door jamb, the cavity must be airtight and filled with insulation snuggly fitted in the space.

p.401(c) Narrow spaces less than 2 inches in width, such as between studs at building corners, and at

p.401the intersection of interior partition walls to exterior walls, shall be filled with insulation snuggly fitted in the space, or with minimally expansive foam sealing.

p.401RA3.5.5.2.2 Special Situations--Installation Prior to Exterior Sheathing or Lath

p.401(a) Hard to access wall stud cavities, such as corner channels, wall intersections, and behind

p.401tub/shower enclosures shall be insulated to the proper R-value. In most cases this can only be completed prior to the installation of the tub/shower enclosure, the exterior sheathing, or the exterior stucco lath.

p.401(b) An air barrier shall be installed on the inside of the exterior wall(s) directly adjacent to the

p.401tub/shower enclosure.

p.401RA3.5.5.2.3 Special Situations--Obstructions

p.401(a) Penetrations and obstructions to the insulation shall be completely caulked and sealed.

p.401(b) Insulation shall fill between the sheathing and the rear of electrical boxes and phone boxes.

p.401RA3.5.5.2.4 Special Situations--Rim Joists

p.401(a) All rim-joists shall be insulated to the same R-value as the adjacent walls.

p.401(b) The insulation shall be installed without gaps and voids.

p.401RA3.5.5.2.5 Special Situations--Kneewalls and Skylight Shafts

p.401(a) Framing for kneewalls and skylight shafts that separate conditioned from unconditioned

p.401space shall be insulated to meet or exceed the wall R-value specified on the Certificate of Compliance, and all other required compliance documentation.

p.401(b) Steel-framed kneewalls and skylight shafts shall meet or exceed the mandatory minimum

p.401insulation requirements and external surfaces of steel studs shall be covered with continuous insulation unless otherwise specified on the Certificate of Compliance using correct U-factors from Joint Appendix JA4, Table 4.3.4 (or U-factors approved by the Commission Executive Director).

p.401(c) The backside of air permeable insulation exposed to the unconditioned attic space shall be

p.401completely covered with a continuous air barrier.