RA3.5.5.1.1 R-value Measurement Equipment

p.4002025 Residential Appendices must use fire retardant facings which have been tested and certified not to exceed a flame spread index (FSI) of 25 and a smoke development index (SDI) of 450. Insulation facings that do not touch a ceiling, wall, or floor surface, and faced batts on the undersides of roofs with an air space between the ceiling and facing are considered exposed applications.

p.400(d) Materials shall be installed according to manufacturer specifications and instructions.

p.400(e) Rigid board insulation shall be attached according to the manufacturer's specifications.

p.400(f) Rigid board insulation may be used as the air barrier provided it has been tested to

p.400conform to the air barrier performance conditions of the Standards.

p.400RA3.5.5.1.1 R-value Measurement Equipment

p.400The ECC-raters shall verify the installed thickness of insulation in all assemblies and locations on walls, roof/ceilings, and floors, and to ensure that insulation levels and installation integrity meet the R-value specified on the Certificate of Compliance, and all other required compliance documentation.

p.400RA3.5.5.1.2 Certificates

p.400All provisions of Residential Appendix RA2 shall be met. All Insulation Certificates of Installation signed by the insulation installer shall be provided stating the installation is consistent with the Certificate of Compliance, plans and specifications for which the building permit was issued. The insulation installer shall also complete the applicable sections of the Certificate of Installation form and attach a product specification or data sheet for every insulation material used.

p.400RA3.5.5.1.3 Certificates and Availability

p.400All provisions of Residential Appendix RA2 shall be met. The Insulation Certificate of Installation, with insulation material labels or specification/data sheets attached, signed by the insulation installer, shall be available on the building site for each of the ECC-rater's verification inspections. Note: The ECC-rater cannot verify compliance credit without these completed forms.

p.400RA3.5.5.2 Wall Insulation

p.400(a) Wall stud cavities shall be caulked, foamed, or otherwise sealed to provide a substantially air­

p.400tight envelope to the outdoors, attic, garage and crawl space. All plumbing and wiring penetrations through the top and bottom plates and electrical boxes that penetrate the sheathing shall be sealed. All gaps in the air barrier shall be caulked or sealed with minimally expansive foam.

p.400(b) Bottom plates of framed and non-framed assemblies shall be sealed to the ground subfloor or

p.400slab, and above ground subfloor.

p.400(c) Installation shall uniformly fit across the plane of the wall and taping and/or caulking of all

p.400joints and seams of the insulation shall be maintained to be considered as the air barrier.

p.400– Residential Field Verification and Diagnostic Test Protocols