RA3.5.5.4.2 Homes with Conditioned Space Over Garage

p.4042025 Residential Appendices RA3.5.5.4.2 Homes with Conditioned Space Over Garage

p.404The separation between conditioned space (house) and the garage shall be insulated with fully supported rigid board insulation to create a continuous thermal barrier. All rim and band joists adjoining conditioned space shall be airtight and insulated.

p.404RA3.5.5.4.3 Homes with No Conditioned Space Over Garage

p.404The band joist where the garage transitions to an attic above conditioned space shall have an air barrier installed in contact with the edge of the attic insulation.

p.404RA3.5.6 SPRAY POLYURETHANE FOAM INSULATION

p.404These procedures detail the installation and inspection protocols necessary to qualify for Quality Insulation Installation (QII) of spray polyurethane foam (SPF) insulation. These procedures must be field verified before the building construction permit is finalized.

p.404These procedures are to be followed by the insulation installer and an ECC-rater must verify its conformance for meeting the requirements of Sections 150.1(c) and 110.7of the Standards.

p.404These procedures apply to two types of SPF used as building insulation: medium density closed cell SPF (ccSPF) and low-density open cell SPF (ocSPF). Most often, the same procedures will apply to both ccSPF and ocSPF. However, in some construction situations the procedures will be different.

p.404RA3.5.6.1 Thermal Specification

p.404RA3.5.6.1.1 ccSPF

p.404A spray applied polyurethane foam insulation having a closed cellular structure resulting in an installed nominal density of 1.5 to less than 2.5 pounds per cubic foot (pcf).

p.404R-value: The total R-value shall be calculated based on the nominal required thickness of the insulation multiplied by a thermal resistivity of 5.8 per inch. The R-value of ccSPF insulation shall meet or exceed the installed thickness specified in Table 3.5-1 below.

p.404Alternatively, the total R-value may be calculated based on the thickness of insulation multiplied by the "tested R-value per inch" as certified by the Department of Consumer Affairs, Bureau of Household Goods and Services. Supporting documentation showing the certified R-value per inch shall be made available at the site for verification and noted on the Certificate of Installation. Based on this calculation, the overall assembly U-factor shall be determined by selecting the assembly type, framing configuration, and cavity insulation from the appropriate Reference Joint Appendix JA4 table or other approved method specified in Section JA4 of the Reference Appendices.

p.404The R-value of the installed insulation shall be based on the verified thickness at an R-value of 5.8 per inch unless supporting documentation is provided that verifies use of other values. Approved

p.404– Residential Field Verification and Diagnostic Test Protocols