p.3982025 Residential Appendices (c) Loose-fill insulation shall be properly supported where necessary to avoid sagging, gaps,
p.398voids, and compression.
p.398RA3.5.4.3.1 Homes with Floors Over Garage
p.398(a) Loose-fill insulation shall be in contact with the air barrier - usually the subfloor.
p.398(b) On floors that are over garages, or where there is an air space between the insulation and the
p.398subfloor, the rim joist shall be insulated.
p.398(c) Loose-fill insulation shall completely fill around wiring and plumbing.
p.398(d) Loose-fill insulation shall be properly supported to avoid sagging, gaps, voids, and
p.398compression.
p.398RA3.5.4.3.2 Homes with Conditioned Space Over Garage
p.398The separation between conditioned space (house) and the garage shall be insulated with fully supported loose-fill insulation to create a continuous thermal barrier. All rim and band joists adjoining conditioned space shall be airtight and insulated.
p.398Figure RA3.5-3 Homes with Conditioned Space Over Garage – Loose Fill Insulation
p.398RA3.5.4.3.3 Homes with No Conditioned Space Over Garage
p.398The band joist where the garage transitions to an attic above conditioned space shall have an air barrier installed in contact with the edge of the attic insulation.
p.398– Residential Field Verification and Diagnostic Test Protocols