RA3.5.4.2.15 Special Situations--Attic Access

p.3972025 Residential Appendices RA3.5.4.2.15 Special Situations--Attic Access

p.397Permanently attach rigid board insulation or batt or blanket insulation with the appropriate R- value to the access door using adhesive or mechanical fastener. The bottom of the attic access shall be gasketed to prevent air leakage of conditioned air to the unconditioned attic.

p.397RA3.5.4.2.16 Special Situations--Below Roof Deck Insulation (Vented and Unvented Attics)

p.397(a) Below roof deck loose-fill insulation shall be netted and installed per manufacturer's

p.397specifications.

p.397(b) For vented attics, below deck loose-fill insulation shall be installed in a manner that does not

p.397obstruct soffit, eave, ridge, or eyebrow vents to allow for adequate attic ventilation. Netting shall be installed in a manner that allows for the required net free area of soffit, eave, gable, and roof vents to be maintained after being filled. Eave vent baffles shall be installed to prevent air movement under or into the insulation.

p.397(c) Netting shall be installed to seal around conduit, plumbing, roof penetrations and all other

p.397obstructions that penetrate the netting.

p.397(d) Loose-fill insulation shall be installed uniformly in the netted cavity side-to-side, top-to­

p.397bottom, and front-to-back and be in continuous contact with the roof sheathing. Loose-fill insulation shall be installed to fit around wiring, conduit, plumbing, and other obstructions.

p.397(e) The installer shall certify on the Certificate of Installation compliance documents that the

p.397manufacturer's minimum weight-per-square-foot requirement has been met.

p.397(f) The ECC-Rater shall verify that the manufacturer's minimum insulation thickness and

p.397specified R-value has been installed.

p.397(g) The ECC-Rater shall verify the minimum weight-per-square-foot requirement has been met.

p.397Verification shall be determined using manufacturer's recommended verification procedures. The ECC-Rater shall record the weight-per-square-foot of the sample on the Certificate of Verification.

p.397(h) Box netted installations are where netting is suspended from the top of roofing framing

p.397member, or top chord, to provide a fill depth that completely encloses the top chord, creating a uniform insulation layer of loose-fill insulation across the entire underside of the roof deck. For these installations, netted insulation cavity thickness shall be uniform and meet the minimum insulation thickness.

p.397(i) For draped netted installations, where netting is attached directly to the bottom of the roof

p.397framing member, the ECC-Rater shall verify that average insulation depth in the cavity meets the depth as specified by the Certificate of Compliance.

p.397RA3.5.4.3 Raised Floors

p.397(a) Loose-fill insulation shall be in contact with the air barrier - usually the subfloor.

p.397(b) Loose-fill insulation shall completely fill around wiring and plumbing.

p.397Appendix RA3– Residential Field Verification and Diagnostic Test Protocols