RA3.5.4.2.12 Special Situations--Enclosed Rafter Ceilings

p.3962025 Residential Appendices (i) Insulation shall be blown to a uniform thickness throughout the attic with all areas meeting or

p.396exceeding the insulation manufacturer's minimum requirements for depth and weight-per­ square-foot.

p.396(j) The installer shall certify on the Certificate of Installation forms that the manufacturer's

p.396minimum weight-per-square-foot requirement has been met.

p.396(k) The ECC-rater shall verify that the manufacturer's minimum weight-per-square-foot

p.396requirement has been met for attics insulated with loose-fill insulation. Verification shall be determined using the methods of the Insulation Contractor’s Association of America (ICAA) Technical Bulletin #17 or #33 except that only one sample shall be taken in the area that appears to have the least amount of insulation. The rater shall record the weight-per-square­ foot of the sample on the Certificate of Verification.

p.396(l) The ECC-rater shall verify that the manufacturer’s minimum insulation thickness has been

p.396installed. For cellulose insulation, this verification shall take into account the time that has elapsed since the insulation was installed. At the time of installation, the insulation shall be greater than or equal to the manufacturer’s minimum initial insulation thickness. If the ECC- rater does not verify the insulation thickness at the time of installation, and if the insulation has been in place less than fourteen days, the insulation thickness shall be greater than the manufacturer’s minimum required thickness to achieve the given R-value at the time of installation, less 1/2 inch to account for settling. If the insulation has been in place for fourteen days or more, the insulation thickness shall be greater than or equal to the manufacturer’s minimum required settled thickness to achieve the given R-value.

p.396RA3.5.4.2.12 Special Situations--Enclosed Rafter Ceilings

p.396(a) An air space shall be maintained between the insulation and roof sheathing as specified by

p.396California Building Code Sections 1203.2 and R806.2, or as specified by the local building department.

p.396(b) Insulation installed in unvented rafter ceilings or to the underside of unvented roofs with an

p.396attic below shall have an R-value conforming to compliance documentation and the air barrier shall be uniform across the transition of roof to wall. The insulation shall be in contact with the air barrier.

p.396RA3.5.4.2.13 RESERVED

p.396RA3.5.4.2.14 Special Situations--HVAC Platform

p.396(a) Loose-fill insulation shall be placed below any platform or catwalk for HVAC equipment

p.396installation and access.

p.396(b) Loose-fill insulation shall be installed so that it will be in contact with the air barrier.

p.396(c) Loose-fill insulation shall be installed under HVAC platform to the full depth and rated R-value

p.396as specified on the Certificate of Compliance, without gaps or compression. If necessary, HVAC platform shall be raised to accommodate ceiling insulation.

p.396– Residential Field Verification and Diagnostic Test Protocols