p.3952025 Residential Appendices RA3.5.4.2.9 Special Situations--Window and Door Headers
p.395(a) All single-member window and door headers shall be insulated to a minimum of R-3 for a 2x4
p.395framing, or equivalent width, and a minimum of R-5 for all other assemblies. Insulation is to be placed between the interior face of the header and inside surface of the interior wall finish.
p.395(b) No header insulation is required for single-member headers that are the same width as the
p.395wall, provided that the entire wall has at least R-2 insulation.
p.395RA3.5.4.2.10 Special Situations--Gable Ends in Unvented Attics
p.395(a) In unvented attics, where insulation is applied directly to the underside of the roof deck,
p.395framing for gable ends that separate the unvented attic from unconditioned space shall be insulated to meet or exceed the wall R-value of the adjacent exterior wall construction as specified on the Certificate of Compliance.
p.395(b) The backside of air permeable insulation exposed to the unconditioned attic space shall be
p.395completely covered with a continuous air barrier.
p.395RA3.5.4.2.11 Roof/Ceilings
p.395(a) Hard covers or draft stops shall be placed over all drop ceiling areas and interior wall cavities
p.395to keep insulation in place and stop air movement. If hard covers or draft stops are missing or incomplete, they shall be completed before insulation is installed or the entire drop area shall be filled with loose-fill insulation level with the rest of the attic.
p.395(b) Baffles shall be placed at eaves or soffit vents of vented attics to keep insulation from
p.395blocking eave ventilation and prevent air movement under or into the insulation. The required net-free ventilation shall be maintained.
p.395(c) Attic rulers appropriate to the material shall be installed and evenly distributed throughout
p.395the attic to verify depth: one ruler for every 250 square feet and clearly readable from the attic access. Attic rulers shall be scaled to read inches of insulation and the R-value installed.
p.395(d) Insulation shall be applied underneath and on both sides of obstructions such as cross-bracing
p.395and wiring.
p.395(e) Insulation shall be applied all the way to the outer edge of the wall top plate.
p.395(f) All recessed light fixtures that penetrate the ceiling shall be listed for zero clearance
p.395insulation contact (IC), have a label that certifies it as airtight with leakage less than 2.0 cfm @ 75 Pa when tested to ASTM E283, and shall be sealed with a gasket or caulk between the light's housing and the ceiling.
p.395(g) Insulation shall cover recessed lighting fixtures. Fixtures that are not rated for insulation
p.395contact (IC), and airtight, shall be removed and/or replaced.
p.395(h) Insulation shall be kept away from combustion appliance flues in accordance with flue
p.395manufacturer's installation instructions or labels on the flue.