p.3882025 Residential Appendices (i) All recessed light fixtures that penetrate the ceiling shall be listed for zero clearance
p.388insulation contact (IC), have a label that certifies it as airtight with leakage less than 2.0 cfm @ 75 Pa when tested to ASTM E283, and shall be sealed with a gasket or caulk between the light's housing and the ceiling.
p.388(j) Insulation shall cover all recessed lighting fixtures. Fixtures that are not rated for insulation
p.388contact (IC), and air-tight, shall be removed and/or replaced.
p.388(k) Facings and insulation shall be kept away from combustion appliance flues in accordance with
p.388flue manufacturer's installation instructions or labels on the flue.
p.388RA3.5.3.3.1 Special Situations--Enclosed Rafter Ceilings
p.388(a) In vented rafter ceilings, an air space shall be maintained between the insulation and roof
p.388sheathing as specified by California Building Code, Sections 1203.2 and R806.3, or as specified by the local building department.
p.388(b) Insulation installed in unvented rafter ceilings or to the underside of unvented roofs with an
p.388attic below shall have an R-value conforming to compliance documentation and the air barrier shall be uniform across the transition of roof to wall. The insulation shall be in contact with the air barrier.
p.388RA3.5.3.3.2 RESERVED
p.388RA3.5.3.3.3 Special Situations--HVAC Platform
p.388(a) Batt and blanket insulation shall be placed below all platforms or cat-walks used for HVAC
p.388equipment installation and access.
p.388(b) Batt and blanket insulation shall be installed so that they will be in contact with the air
p.388barrier.
p.388(c) Batt and blanket insulation shall be installed under HVAC platform to the full depth and rated
p.388R-value as specified on the Certificate of Compliance, without gaps or compression. If necessary, HVAC platform shall be raised to accommodate ceiling insulation.
p.388RA3.5.3.3.4 Special Situations--Attic Access
p.388Permanently attach rigid board insulation or batt or blanket insulation with the appropriate R- value to the access door using adhesive or mechanical fastener. The bottom of the attic access shall be gasketed to prevent air leakage of conditioned air to the unconditioned attic.
p.388RA3.5.3.3.5 Special Situations--Below Roof Deck Insulation (Vented and Unvented Attics)
p.388(a) Below roof deck insulation consisting of batts that nominally fill the cavity space between
p.388roof framing members shall be stapled, or supported with cabling, tension rods, or other support measures which maintain the batt uniformly against the roof deck with limited compression. Batts with facing directed to the attic space shall be face stapled. Inset stapling of underside batts is not allowed. Batts supported with cabling, tensions rods, or other methods supporting the batt from below shall be supported at intervals less than or equal to
p.388– Residential Field Verification and Diagnostic Test Protocols