p.3872025 Residential Appendices (c) Insulation shall be applied to fully enclose and/or adhere to all sides and ends of structural
p.387assembly framing that separate conditioned from unconditioned space.
p.387(d) The structural portions of assemblies shall be air-tight.
p.387RA3.5.3.2.9 Special Situations--Window and Door Headers
p.387(a) All single-member window and door headers shall be insulated to a minimum of R-3 for a 2x4
p.387framing, or equivalent width, and a minimum of R-5 for all other assemblies. Insulation is to be placed between the interior face of the header and inside surface of the interior wall finish.
p.387(b) No header insulation is required for single-member headers that are the same width as the
p.387wall, provided that the entire wall has at least R-2 insulation.
p.387RA3.5.3.2.10 Special Situations--Gable Ends in Unvented Attics
p.387(a) In unvented attics, where insulation is applied directly to the underside of the roof deck,
p.387framing for gable ends that separate the unvented attic from the exterior or unconditioned space shall be insulated to meet or exceed the wall R-value of the adjacent exterior wall construction as specified on the Certificate of Compliance.
p.387(b) The backside of air permeable insulation exposed to the unconditioned attic space shall be
p.387completely covered with a continuous air barrier.
p.387RA3.5.3.3 Roof/Ceilings
p.387(a) Batt and blanket insulation shall be correctly sized to fit snugly at the sides and ends.
p.387(b) Batt and blanket insulation shall be installed to be in contact with the air barrier.
p.387(c) Where necessary, batt and blanket insulation shall be cut to fit properly - there shall be no
p.387gaps, nor shall the insulation be doubled-over or compressed.
p.387(d) When batt and blanket insulation are cut to fit a non-standard cavity, they shall be snuggly
p.387fitted to fill the cavity with limited compression.
p.387(e) Batt and blanket insulation shall be cut to butt-fit around wiring and plumbing, or be split
p.387(delaminated) so that one layer can fit behind the wiring or plumbing, and one layer fit in front.
p.387(f) Batt and blanket insulation that is thicker than the framing depth shall be installed so that the
p.387insulation expands to touch adjacent insulation over each framing member.
p.387(g) Hard covers or draft stops shall be placed over all drop ceiling areas and interior wall cavities
p.387to keep insulation in place and stop air movement. If hard covers or draft stops are missing or incomplete, they shall be completed before insulation is installed.
p.387(h) Baffles shall be placed at eaves or soffit vents of vented attics to keep insulation from
p.387blocking eave ventilation and prevent air movement under the insulation. The required net- free ventilation shall be maintained.