RA3.5.3.2.1 Narrow-Framed Cavities

p.3852025 Residential Appendices (f) When batt and blanket insulation are cut to fit a non-standard framing, they shall be snuggly

p.385fitted to fill the cavity with limited compression.

p.385(g) Batt insulation shall be cut to butt-fit around wiring and plumbing, or be split (delaminated)

p.385so that one layer can be fit behind the wiring or plumbing, and one layer fit in front. The layers must be proportional to the obstruction's position in the cavity to avoid compression and voids.

p.385RA3.5.3.2.1 Narrow-Framed Cavities

p.385(a) Non-standard width cavities shall be filled with insulation to snuggly fit into the space, or with

p.385minimally expansive foam sealing material.

p.385(b) Narrow spaces less than 1 inch in width at windows and door jambs, shall be filled with

p.385minimally expansive foam sealing. In cases where the manufacturer’s warranty would be void if minimally expansive foam is used to seal the gap between the window frame or door jamb, the cavity must be airtight and batt insulation cut to width and snuggly fitted (with limited compression) in the space.

p.385(c) Narrow spaces less than 2 inches in width, such as between studs at building corners, and at

p.385the intersection of interior partition walls to exterior walls, shall be filled with insulation snuggly fitted in the space, or with minimally expansive foam sealing.

p.385RA3.5.3.2.2 Special Situations--Installation Prior to Exterior Sheathing or Lath

p.385(a) Hard to access wall stud cavities, such as corner channels, wall intersections, and behind

p.385tub/shower enclosures shall be insulated to the proper R-value. In most cases this can only be completed prior to the installation of the tub/shower enclosure, the exterior sheathing, or the exterior stucco lath.

p.385(b) An air barrier shall be installed on the inside of the exterior wall(s) directly adjacent to the

p.385tub/shower enclosure.

p.385RA3.5.3.2.3 Special Situations--Obstructions

p.385(a) Insulation shall be delaminated or cut to fit around wiring, plumbing, vents, and other

p.385obstructions with limited compression. Compression of insulation in these situations is limited to ≤ 30% of its nominal thickness.

p.385(b) Insulation shall be placed between the sheathing and the rear of electrical boxes and other

p.385obstructions that are not as deep as the cavity (i.e., communications boxes, medicine cabinets).

p.385(c) In cold climates, where water pipes may freeze (such as Climate Zones 2, 11-14 and 16) pipes

p.385shall have at least 1/2 of the insulation between the water pipe and towards the outside surface of the exterior wall. As much insulation as possible shall be placed between the pipe and the outside (without compression), and remaining insulation shall be placed between the pipe and the interior assembly material.

p.385Appendix RA3– Residential Field Verification and Diagnostic Test Protocols