RA3.5.3.1.2 R-value Measurement Equipment

p.3842025 Residential Appendices (i) Batt and blanket insulation shall be cut to butt-fit around wiring and plumbing, or be split

p.384(delaminated) so that one layer can fit behind the wiring or plumbing, and one layer fit in front.

p.384RA3.5.3.1.2 R-value Measurement Equipment

p.384The ECC-rater shall verify the installed thickness of insulation in all assemblies and locations on walls, roof/ceilings, and floors, and to ensure that insulation levels and installation integrity meet the R-value specified on the Certificate of Compliance, and all other required compliance documentation.

p.384RA3.5.3.1.3 Certificates

p.384All provisions of Residential Appendix RA2 shall be met. All Insulation Certificates of Installation signed by the insulation installer shall be provided stating the installation is consistent with the Certificate of Compliance, plans and specifications for which the building permit was issued. The insulation installer shall complete all applicable sections of the Certificate of Installation form and attach a product specification or data sheet for every insulation material used.

p.384RA3.5.3.1.4 Certificates and Availability

p.384All provisions of Residential Appendix RA2 shall be met. The Insulation Certificate of Installation, with insulation material labels or specification/data sheets attached, signed by the insulation installer, shall be available on the building site for each of the ECC-rater’s verification inspections. Note: The ECC-rater cannot verify compliance credit without these completed forms.

p.384RA3.5.3.2 Wall Insulation

p.384(a) Wall stud cavities shall be caulked, foamed, or otherwise sealed to provide a substantially air­

p.384tight envelope to the outdoors, attic, garage and crawl space. All plumbing and wiring penetrations through the top and bottom plates and electrical boxes that penetrate the sheathing shall be sealed. All gaps in the air barrier shall be caulked, taped, or sealed with minimally expansive foam.

p.384(b) Bottom plates of framed and non-framed assemblies shall be sealed to the ground subfloor or

p.384slab, and above ground subfloor.

p.384(c) Insulation shall uniformly fill the cavity side-to-side, top-to-bottom, and front-to-back.

p.384(d) Batt insulation shall fill the cavity by friction fitting, inset or face stapling of flanges of faced

p.384batts, or by other support methods as necessary.

p.384(e) Batt and blanket insulation shall be installed to fill the cavity and be in contact with the

p.384sheathing on the back and the wallboard on the front – no gaps or voids.

p.384– Residential Field Verification and Diagnostic Test Protocols