p.383RA3.5.3 BATT AND BLANKET INSULATION
p.383These procedures detail the installation and inspection protocols necessary to qualify for Quality Insulation Installation (QII) of batt and blanket insulation. These procedures must be field verified before the building construction permit is finalized.
p.383These procedures are to be followed by the insulation installer and an ECC-rater must verify its conformance to meet the requirements of Sections 150.1(c)1E or 170.2(a)6, and 110.7 of the Standards.
p.383RA3.5.3.1 Thermal Specification
p.383This insulation type is manufactured in different widths, lengths, and thicknesses and is available with or without a facing. Faced batts and blanket insulation material are also available with or without an attachment flange. Specific product R-values are readily available from the manufacturer for the specific materials being installed and the R-value of the product is marked on the face of the product (faced or unfaced material). The installed insulation must meet the R- value stated on the compliance documentation.
p.383RA3.5.3.1.1 Requirements for Walls, Roof/Ceilings and Floors
p.383(a) Materials shall comply with, and be installed in conformance with, all applicable building
p.383codes for building. California Building Code (including, but not limited to, California Electric Code Section 719) and installed to meet all applicable fire codes.
p.383(b) Materials shall meet California Quality Standards for Insulating Material, Title 24, Part 12,
p.383Chapter 4, Article 3, listed in the California Department of Consumer Affairs Consumer Guide and Directory of Certified Insulating Materials.
p.383(c) Materials shall comply with flame spread rating and smoke density requirements of Chapter
p.38326 and Section 706 of the Title 24, Part 2: all installations with exposed facings must use fire retardant facings which have been tested and certified not to exceed a flame spread index (FSI) of 25 and a smoke development index (SDI) of 450. Insulation facings that do not touch a ceiling, wall, or floor surface, and faced batts on the undersides of roofs with an air space between the ceiling and facing are considered exposed applications.
p.383(d) Materials shall be installed according to manufacturer specifications and instructions.
p.383(e) Batt and blanket insulation shall be correctly sized to fit snugly at the sides and ends.
p.383(f) Batt and blanket insulation shall be installed so that they will be in contact with the air
p.383barrier.
p.383(g) Where necessary, batt and blanket insulation shall be cut to fit properly - there shall be no
p.383gaps, nor shall the insulation be doubled-over or compressed.
p.383(h) When batt and blanket insulation are cut to fit a non-standard cavity, they shall be snuggly
p.383fitted to fill the cavity without compression.