p.3632025 Residential Appendices RA3.3.2.2.3 Digital Utility Revenue Meter
p.363The apparatus for measuring the air handler watt draw shall consist of the digital utility revenue meter meeting the applicable instrumentation specifications in RA3.3.1 that provides direct digital display of the Watt draw. All registers and blower access panel(s) shall be in their normal operating condition.
p.363RA3.3.3 Procedures
p.363RA3.3.3.1 System Airflow Rate Measurement Procedures
p.363When required for compliance, the installed system's airflow shall be diagnostically tested using one of the methods specified in this section.
p.363For systems utilizing an intentional ducted ventilation airflow from outside the conditioned space into the return system, the outside airflow may be included in the system airflow if that flow occurs in all operating modes of the HVAC system.
p.363Diagnostic system airflow rate measurement values shall be converted to fan cfm/ton by dividing the measured system airflow rate (Qah) by the nominal tons of condensing unit cooling capacity for the air conditioner.
p.363The measured airflow rate shall be expressed in cubic feet per minute of standard air (standard air has a density of 0.075 lb/ft3). When the airflow measurement is made at altitudes significantly different from sea level or at temperatures significantly different from 70°F, the airflow indicated on the device gauge may differ from the standard CFM by as much as 15 percent. Corrections from indicated to standard CFM shall be made using the procedure specified by the airflow measurement device manufacturer.
p.363RA3.3.3.1.1 System Airflow Rate Measurement Using Plenum Pressure Matching and Fan
p.363Flowmeter
p.363This system airflow measurement shall be performed using the following procedures:
p.363(a) If the fan flowmeter is to be connected to the air handler outside the conditioned space,
p.363then the door or access panel between the conditioned space and the air handler location shall be opened.
p.363(b) With the system fan on at the maximum speed used in the installation (the cooling speed
p.363when air conditioning is present), measure the pressure difference (in Pa) between the supply plenum and the conditioned space (Psp). Psp is the target pressure to be maintained during the system airflow tests. Place the pressure probe in the Supply Pressure Measurement Location described in Section RA3.3.1.1. Adjust the probe to achieve the highest pressure and then firmly attach the probe to ensure that it does not move during the system airflow test.
p.363(c) If the fan flowmeter is to be connected to the air handler at the access, block the return
p.363duct system from the plenum upstream of the air handler fan and the fan flowmeter. Filters are often located in an ideal location for this blockage.
p.363Appendix RA3– Residential Field Verification and Diagnostic Test Protocols