p.3642025 Residential Appendices (d) Attach the fan flowmeter to the duct system at the inlet to one return duct from the
p.364conditioned space with the grille and filter removed (if there is more than one system return grille, block off all return grilles other than the one used for this measurement. Alternatively, the fan flowmeter may be placed at the air handler.
p.364(e) Turn on the system fan and the fan flowmeter, adjust the fan flowmeter until the
p.364pressure between supply plenum and conditioned space matches Psp.
p.364(f) Record the flow through the fan flowmeter (Qah, cfm) - this is the diagnostic system
p.364airflow. In some systems, system fan and fan flowmeter combinations may not be able to produce enough flow to reach Psp. In this case record the maximum flow (Qmax, cfm) and pressure (Pmax) between the supply plenum and the conditioned space. The following equation shall be used to correct measured system flow and pressure (Qmax and Pmax) to operating condition at operating pressure (Psp).
p.364Equation RA3.3-1 Air Handler Flow
Equation text: Qah = Qmax x (Psp/Pmax) ^0.5
Needs visual review
p.364RA3.3.3.1.2 System Airflow Rate Measurement Using Flow Grid
p.364The system airflow measurement shall be performed using the following procedures:
p.364(a) With the system fan on at the maximum speed used in the installation (the cooling speed
p.364when air conditioning is present), measure the pressure difference (in Pa) between the supply plenum and the conditioned space (Psp). Place the pressure probe in the Supply Pressure Measurement Location described in Section RA3.3.1.1. Adjust the probe to achieve the highest pressure and then firmly attach the probe to ensure that it does not move during the system airflow test.
p.364(b) The flow grid shall be attached at a point where all the system air flows through the flow
p.364grid. If there are multiple return grilles in the duct system, flow grids may be used to measure airflow at the return grilles, but only by installing a flow grid in each return grill and making simultaneous measurements of all return grill airflows.
p.364(c) Re-measure the system operating pressure with the flow grid in place.
p.364(d) Measure the airflow through the flow grid (Qgrid) and the test pressure (Ptest). If multiple
p.364flow grids are used Qgrid is the sum of the flows through each of the flow grids.
p.364(e) The following equation for air handler flow shall be used to correct flow through the flow
p.364grid and pressure (Qgrid and Ptest) to operating condition at operating pressure (Psp).
p.364Equation RA3.3-2 Air Handler Flow
p.364Qah = Qgrid x (Psp/Ptest) ^0.5
p.364– Residential Field Verification and Diagnostic Test Protocols