RA3.1.4.3.5 Sealing of All Accessible Leaks

p.3342025 Residential Appendices (d) Attach a blower door to an external doorway. If the door between the dwelling and the

p.334garage is used, the garage car-bay doors must be open.

p.334(e) If any ducts are located in an unconditioned basement, all doors or accesses between the

p.334conditioned space and the basement shall be closed, and at least one operable door or window (if it exists) between the basement and outside shall be open during the test.

p.334(f) If the ducts are located in a conditioned basement, any door between the basement and

p.334the remaining conditioned space shall be open, and any basement doors or windows to outside must be closed during the test.

p.334(g) Adjust the blower door fan to provide positive 25 Pa (0.1 inches of water) pressure in the

p.334conditioned space with respect to outside.

p.334(h) Adjust the fan/flowmeter to maintain a zero pressure difference (plus or minus 0.5Pa

p.334(.002 inches water)) between the ducts and the conditioned space, and adjust the blower door fan to maintain a positive 25 Pa (0.1 inches of water) pressure in the conditioned space with respect to outside. This step may require several iterations.

p.334(i) Record the flow through the flowmeter; this is the duct leakage flow to outside at 25 Pa

p.334(0.1 inches water). If the leakage flow is less than or equal to the applicable compliance criteria required by the Standards, the system passes.

p.334(j) If required for compliance, divide the leakage flow by the system air handler airflow

p.334determined by the procedure in Section RA3.1.4.2, and convert to a percentage. If the leakage flow percentage is less than or equal to the criterion required by the Standards, the system passes.

p.334RA3.1.4.3.5 Sealing of All Accessible Leaks

p.334For altered existing duct systems that are unable to pass either the Fan Pressurization of Ducts test (RA3.1.4.3.1), or the Duct Leakage to Outside test (RA3.1.4.3.4)), the objective of this test is to verify that all accessible leaks are sealed. The following procedure shall be used:

p.334(a) Complete the leakage test specified in Section RA3.1.4.3.1 to measure the leakage before

p.334commencing duct sealing.

p.334(b) Seal all accessible ducts.

p.334(c) After sealing is complete, again use the procedure in RA3.1.4.3.1 to measure the leakage

p.334after duct sealing.

p.334(d) Complete the Smoke Test as specified in RA3.1.4.3.6.

p.334(e) Complete the Visual Inspection as specified in RA3.1.4.3.7.

p.334RA3.1.4.3.6 Smoke-Test of Accessible-Duct Sealing

p.334For altered existing ducts that fail the leakage tests, the objective of the smoke test is to confirm that all accessible leaks have been sealed. The following procedure shall be used:

p.334Appendix RA3– Residential Field Verification and Diagnostic Test Protocols