RA3.1.4.3.3 Installer Visual Inspection at Final Construction Stage

p.3332025 Residential Appendices (e) Insert a static pressure probe at one of the sealed supply duct boots, or return duct boxes,

p.333located at a point in the system close to the fan flowmeter.

p.333(f) Adjust the fan flowmeter to produce a positive 25 Pa (0.1 inches water) pressure at the

p.333supply plenum with respect to the outside or with respect to the building space with the entry door open to the outside.

p.333(g) Record the airflow through the flowmeter; this is the leakage flow at 25 Pa (0.1 inches

p.333water).

p.333(h) If the supply and return ducts are tested separately, repeat items 4 through 6 with the

p.333flow meter attached to the unsealed return box and the static pressure probe in the return duct boxes, located at a point in the system close to the fan flowmeter, then add the two leakage rates together to get a total leakage flow.

p.333(i) Divide the leakage flow by the total air handler airflow determined by the procedure in

p.333Section RA3.1.4.2 and convert to a percentage. If the leakage flow percentage is less than or equal to the compliance criterion required by the Standards, the system passes.

p.333RA3.1.4.3.3 Installer Visual Inspection at Final Construction Stage

p.333After installing the interior finishing drywall, or other finishing material, and verifying that one of the above rough-in tests was completed, the following procedure shall be used:

p.333(a) Remove at least one supply and one return register, and verify that the spaces between

p.333the register boot and the interior finishing wall are properly sealed.

p.333(b) If the house rough-in duct leakage test was conducted without an air handler installed,

p.333inspect the connection points between the air handler and the supply and return plenums to verify that the connection points are properly sealed.

p.333(c) Inspect all joints to ensure that no cloth backed rubber adhesive duct tape is used.

p.333RA3.1.4.3.4 Duct Leakage to Outside from Fan Pressurization of Ducts

p.333The objective of this test is to determine the amount of duct leakage to outside the air barrier for the conditioned space. This measurement is utilized to verify that duct systems are located entirely within conditioned space. The procedure is also utilized to provide an alternate leakage measurement for situations when it is likely that a portion of the total duct leakage is inside the air barrier for the conditioned space. The duct leakage to outside shall be determined by pressurizing the ducts and the conditioned space of the house to 25 Pa (0.1 inches water) with respect to outside. The following procedure shall be used for the fan pressurization test of leakage to outside:

p.333(a) Seal all the supply registers and return grilles except for one large centrally located return

p.333grille or the air handler cabinet access panel.

p.333(b) Attach the fan flowmeter device to the duct system at the unsealed return grille or the air

p.333handler cabinet access panel.

p.333(c) Install a static pressure probe at the supply plenum.

p.333Appendix RA3– Residential Field Verification and Diagnostic Test Protocols