RA3.1.4.3.2 Diagnostic Duct Leakage at Rough-in Construction Stage

p.3312025 Residential Appendices pressurizing the entire duct system to a positive pressure of 25 Pa (0.1 inches water) with respect to outside. The following procedure shall be used for the fan pressurization tests:

p.331(a) Verify that the air handler, supply and return plenums and all the connectors, transition

p.331pieces, duct boots and registers are installed and sealed. The entire duct system shall be included in the total leakage test.

p.331(b) For newly installed or altered ducts, verify that cloth backed rubber adhesive duct tape

p.331has not been used and if a platform or other building cavity used to house the air distribution system has been newly installed or altered, it contains a duct or is ducted with duct board or sheet metal.

p.331(c) Seal all the supply registers and return grilles except for one large centrally located return

p.331grille or the air handler cabinet access panel. Floor registers on carpeted floors may be removed and the opening sealed to the floor under the carpet. If allowed by the equipment manufacturer, the air-handling unit blower compartment access panel may be sealed with an approved tape - do not use mastic or other permanent sealing material.

p.331(d) Attach the fan flowmeter device to the duct system at the unsealed return grille or the air

p.331handler cabinet access panel. Ensure that the air filter has been removed.

p.331(e) Install a static pressure probe at a supply register located close to the air handler, or at

p.331the supply plenum.

p.331(f) Adjust the fan flowmeter to produce a positive 25 Pa (0.1 inches water) pressure at the

p.331supply register or the supply plenum with respect to the outside or with respect to the building space with the entry door open to the outside.

p.331(g) Record the flow through the flowmeter; this is the leakage flow at 25 Pa (0.1 inches

p.331water).

p.331(h) Divide the leakage flow by the total air handler airflow determined by the procedure in

p.331Section RA3.1.4.2 and convert to a percentage. If the leakage flow percentage is equal to or less than the compliance criterion required by the Standards, the system passes.

p.331RA3.1.4.3.2 Diagnostic Duct Leakage at Rough-in Construction Stage

p.331Installers may determine duct leakage in newly constructed buildings by using diagnostic measurements at the rough-in building construction stage prior to installation of the interior finishing. When using this measurement technique, the installer shall complete additional inspection (as described in section RA3.1.4.3.3) of duct integrity after the finishing wall has been installed. In addition, after the finishing wall is installed, spaces between the register boots and the wallboard shall be sealed. Cloth backed rubber adhesive duct tapes shall not be used to seal the space between the register boot and the wall board.

p.331The duct leakage measurement at rough-in construction stage shall be performed using a fan pressurization device. The duct leakage shall be determined by pressurizing both the supply and return ducts to 25 Pa (0.1 inches water). The following procedure (either RA3.1.4.3.2.1 or RA3.1.4.3.2.2) shall be used:

p.331Appendix RA3– Residential Field Verification and Diagnostic Test Protocols