p.3302025 Residential Appendices
| duct leakage testing. However, the ventilation ventilation airflow is required and close when during space conditioning system duct l eakage Table RA3.1-2 summarizes the leakage test compliance. Table RA3.1-2 – Duct Leakage Verification and | system motorized dampers that ventilation airflow is not required testing. procedures that may be used to Diagnostic Test Protocols | open only when may be closed demonstrate |
| Verification Description | User Application | Procedure(s) |
| Sealed and tested new duct systems in single family homes and townhomes | Installer Testing at Final ECC-Rater Testing | RA3.1.4.3.1 |
| Sealed and tested new duct systems in single family homes and townhomes | Installer Testing at Rough-in, Air Handling Unit Installed | RA3.1.4.3.2 RA3.1.4.3.2.1 RA3.1.4.3.3 |
| Sealed and tested new duct systems in single family homes and townhomes | Installer Testing at Rough-in, Air Handling Unit Not Installed | RA3.1.4.3.2 RA3.1.4.3.2.2 RA3.1.4.3.3 |
| Sealed and tested new duct systems in multifamily homes regardless of duct system location. | Installer Testing at Final ECC-Rater Testing | RA3.1.4.3.1 |
| Sealed and tested new duct systems in multifamily homes regardless of duct system location. | Installer Testing at Final ECC-Rater Testing | RA3.1.4.3.4 |
| Verification of Low Leakage Air Handler with Sealed and Tested Duct System Compliance Credit | Installer Testing at Final ECC-Rater Testing | RA3.1.4.3.1 and RA3.1.4.3.9 |
| Verification of low leakage ducts located entirely in conditioned space | Installer Testing ECC-Rater Testing | RA3.1.4.3.8 |
| Sealed and tested altered existing duct systems | Installer Testing ECC-Rater Testing | RA3.1.4.3.1 |
| Sealed and tested altered existing duct systems | Installer Testing ECC-Rater Testing | RA3.1.4.3.4 |
| Sealed and tested altered existing duct systems | Installer Testing and Inspection ECC-Rater Testing and Verification | RA3.1.4.3.5 RA3.1.4.3.6 RA3.1.4.3.7 |
| RA3.1.4.3.1 Diagnostic Duct Leakage from The objective of this procedure is for an installer leakage of a new or altered duct system. The | Fan Pressurization of Ducts to determine or a rater to verify total duct leakage shall be determined the total by |
p.330Appendix RA3– Residential Field Verification and Diagnostic Test Protocols