NA7.20.1.1.2 Functional Testing (Option A: Subcritical Operation)

p.6072025 Nonresidential Appendices NA7.20.1.1.2 Functional Testing (Option A: Subcritical Operation)

p.6082025 Nonresidential Appendices temperature and the refrigeration system saturated condensing temperature (SCT).

p.607Planning: The system cooling load must be sufficiently high, and ambient conditions sufficiently below the critical point, to operate subcritically with all gas cooler fans in operation and observe controls in average conditions. Account for weather conditions in scheduling testing by, if necessary, artificially increasing or decreasing evaporator loads in order to perform the Functional Testing at typical system conditions.

p.608(d) Confirm agreement between the current control system TD setpoint and the

p.608observed TD. If values are different, address and correct control system methods.

p.608Step 4: Test adjusted control TD:

p.607Step 1: Verify mechanical controls and other strategies will not affect tests:

p.608(a) Enter a smaller TD value into the control system, sufficient to cause an

p.608observable response, such as 1-2 degrees smaller, but not small enough to cause system to operate continuously at 100% fan speed. Record this value as TD Test Setpoint 1.

p.607(a) Turn off any heat reclaim controls and any intermittent defrost pressure offset

p.607strategies that would affect gas cooler setpoint control.

p.607(b) If testing an adiabatic gas cooler, adjust setpoints to ensure that the gas cooler

p.608(b) Observe change in control system operation which should include an increase in

p.607stays in “dry” mode or “precool” mode consistently throughout the test.

p.608fan speed and a decrease in condensing temperature.

p.607Step 2: Operate in control range and verify stable control:

p.608(c) Allow time for the control system to achieve stable operation.

p.607(a) Verify the gas cooler control value is operating in the variable setpoint control

p.608(d) Document current head pressure control setpoints, including the TD setpoint.

p.607range, i.e., above the minimum SCT setpoint and below the maximum SCT setpoint.

p.608(e) Calculate and record the actual observed temperature difference (TD), defined as

p.608the difference between the ambient dry bulb or precool air temperature and the refrigeration system saturated condensing temperature (SCT).

p.607• If necessary, increase or decrease the system load.

p.607• If necessary, during low load or low ambient conditions with system observed at the minimum SCT, temporarily adjust the minimum SCT to a lower value, if the refrigeration system design will allow, or increase the control TD to result in a higher control value.

p.608(f) Confirm agreement between the current control system TD setpoint and the

p.608observed TD. If values are different, address and correct control system methods.

p.608(g) Perform the above test sequence with a second TD value, recorded as TD Test

p.607(b) Observe control operation for at least 30 minutes to confirm stable control

p.608Setpoint 2, and record the same values above to confirm agreement between the current control system TD setpoint and the observed TD. If needed perform corrective actions and repeat testing until variable setpoint control can be confirmed and documented.

p.607operation, as shown by gas cooler fan speed varying as compressor capacity changes, and not ranging from maximum to minimum fan speed or constant “hunting”. If required, adjust control response setpoints to achieve stable operation. Note: Since gas cooler control settings require fine-tuning over time, this is often accomplished using control system history or visual trends, showing one hourly and daily operation.

p.608Step 5: Verify and document all fans operate in unison down to minimum SCT:

p.608(a) Document that all fans are in operation, fan speed, actual SCT and control

p.608system minimum SCT setpoint, by recording control system screens or trends along with observations.

p.607Step 3: Identify control TD:

p.607(a) Record the current outdoor ambient air dry bulb or precool air temperature and

p.6081. In cool weather and/or light loads, this may be the observed operation during testing without need to manipulate system setpoints.

p.607refrigeration system condensing temperature/condensing pressure readings from the control system. Note whether discharge pressure or a dedicated gas cooler pressure sensor is used for gas cooler pressure control.

p.6082. In warmer weather and/or higher loads, the control system minimum SCT value can be increased slowly to a value equal to, and then above, the current operating condition, in order to observe the fans operating in unison and fan speeds dropping as the minimum SCT setpoint is achieved.

p.607(b) Document current head pressure control setpoints, including the TD setpoint.

p.607(c) Calculate and record the actual observed temperature difference (TD), defined as

p.607the difference between the ambient dry bulb temperature or precool air

p.607Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processesp.608

p.608Appendix NA7 – Installation and Acceptance Requirements for Nonresidential Buildings and Covered Processes